Midea INVERTER SPLIT TYPE ROOM AIR CONDITIONER Installation Manual page 12

Inverter split type room air conditioner
Hide thumbs Also See for INVERTER SPLIT TYPE ROOM AIR CONDITIONER:
Table of Contents

Advertisement

Warning
Be sure to comply with local codes while
running the wire from the indoor unit to
the outdoor unit.
Every wire must be connected firmly.
No wire should be allowed to touch
refrigerant tubing, the compressor
or any moving parts.
Loose wiring may cause the terminal to
overheat or result in unit malfunction.
A fire hazard may also exit. Therefore,
be sure all wiring is tightly connected.
Disconnecting means must be provided
and shall be located within sight from and
readily accessible from the air conditioner.
Connecting cable with conduit shall go
through the hole of the conduit panel.
ELECTRICAL WORK
Special branch circuit breaker
(Fuse/Breaker capacity:20A)
Note : To prevent wires loosening or leaving
the Cord Clamp, please select proper cord
diameter to fill the holes on the cord clamp.
Terminal block of outdoor unit
L1 L2
To indoor unit
L1 L2
To indoor unit
1(L) 2(N) S
To indoor unit
11
Power supply
cord
Power supply
1φ 208-230V~60Hz
S
L1 L2
To power supply
(1)
S
L1 L2
To power supply
(2)
L
N
To power supply
(3)
Fig.23b

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents