MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Part. 1 General information 1. Model Names of Indoor/Outdoor Units ......3 2. External Appearance ............3 3. Nomenclature ..............5...
Page 4
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 1. Model Names of Indoor/Outdoor Units Indoor unit Outdoor unit Model Power supply Model Power supply IDR3-X 26M 220-240V~, 1Ph, 50/60Hz MCR3-X 26M 220-240V~, 1Ph, 50/60Hz IDR3-X 35M 220-240V~, 1Ph, 50/60Hz...
Page 5
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual 2.2 Outdoor unit MCR3-X 26M/ MCR3-X 35M/ MCR3-X 53M MCR3-X 71M/ MCR3-X 90M MCR3-X 105M/ MCR3-X 140M MCR3-X 160M...
Page 6
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 3. Nomenclature 3.1 Indoor unit I D R3– X Phase type - M: Single phase Capacity type - 26: 2600W Refrigerant type - X: R410A Series number:R3 Medium static pressure Indoor unit 3.2 Outdoor unit...
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 2. Dimension (Unit: mm) MCR3-X 26M/ MCR3-X 35M/ MCR3-X 53M Model 35/53 MCR3-X 71M/ MCR3-X 90M Model 71/90...
Page 11
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCR3-X 105M/ MCR3-X 140M Model 105/140 MCR3-X 160M Model 1040 1053...
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 3. Refrigerant circuit MCR3-X 26M / MCR3-X 35M E S C Compressor Silencer Four-way reversing valve Silencer Condenser Fan blade Motor Heating spool Refrigerant cooling module Throttling capillary Stop valve (liquid side)
Page 13
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCR3-X 53M E S C Compressor Silencer Four-way reversing valve Silencer Condenser Fan blade Motor Heating spool Refrigerant cooling module Refrigeration spool Stop valve (liquid side) Evaporator Indoor unit wind wheel...
Page 14
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 MCR3-X 71M E S C Compressor Silencer Four-way reversing valve Silencer Condenser Fan blade Motor Heating spool Refrigerant cooling module Refrigeration spool Stop valve (liquid side) Evaporator Indoor unit wind wheel...
Page 15
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCR3-X 90M E S C Compressor Silencer Four-way reversing valve Silencer Condenser Fan blade Motor Heating spool Refrigerant cooling module Refrigeration spool Stop valve (liquid side) Evaporator Indoor unit wind wheel...
Page 16
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 IDR3-X 105M、IDR3-X 140M、IDR3-X 160M E S C Compressor Silencer High pressure switch Four-way reversing valve Condenser Fan blade Motor Heating spool Refrigerant cooling module Refrigeration spool Filter Stop valve (liquid side)
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual 4. Wiring Diagrams MCR3-X 26M / MCR3-X 35M MCR3-X 53M / MCR3-X 71M Outdoor wire diagram DC Fan CN414 Four Way Valve CN60 CN23 Debug Board Brown L-IN Outdoor main Controller...
Page 18
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202002 MCR3-X 90M...
Page 19
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCR3-X 105M / MCR3-X 140M...
Page 20
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202002 MCR3-X 160M...
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202002 6. Sound Levels Front (H+1)/2 m Notes: H is the height of ODU Model Noise level under three speeds of fan (dB(A)) MCR3-X 26M MCR3-X 35M MCR3-X 53M MCR3-X 71M...
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Part. 3 Indoor Unit 1.Specifications ..............23 2.Dimensions (Unit: mm) ............26 3.Wiring Diagrams ..............30 4.Capacity Table ..............34 5.Static Pressure Curve ............70 6.Electric Characteristics ............. 74 7.Sound Levels ..............
Page 24
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 1. Specifications Table 1.1: IDR3-X 26(35,53)M specifications Model name IDR3-X 26M IDR3-X 35M IDR3-X 53M Power supply 1-phase, 220-240V, 50/60Hz Capacity 2600(700~3500) 3500 (700~4000) 5300(1000~6000) Input(IDU+ODU) 715(170~1420) 1020(190~1460) 1500(250~2370)
Page 25
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Table 1.2: IDR3-X 71(90)M specifications Model name IDR3-X 71M IDR3-X 90M Power supply 1-phase, 220-240V, 50/60Hz Capacity 7200(2400~8200) 9000 Input(IDU+ODU) 2180(450~3280) 2750 Cooling Input(IDU) 3.30 3.27 Capacity 8600(2100~9600) 10000...
Page 26
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 Table 1.3: IDR3-X 105(140,160)M specifications Model name IDR3-X 105M IDR3-X 140M IDR3-X 160M Power supply 1-phase, 220-240V, 50/60Hz Capacity 10500 14000 16000 Input(IDU+ODU) 3000 4650 5500 Cooling Input(IDU) 3.50 3.01...
Page 27
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual 2. Dimensions (Unit: mm) IDR3-X 26M/ IDR3-X 35M/ IDR3-X 53M/ IDR3-X 71M External dimensions and size of air outlet duct Size of return air inlet (back return air mode)
Page 28
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 IDR3-X 90M External dimensions and size of air outlet duct Size of return air inlet (back return air mode) Size of return air inlet (bottom return air mode), and the distance between the lugs...
Page 29
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual IDR3-X 105M External dimensions and size of air outlet opening Distance between the lugs Size of air inlet opening (air intake from rear) Air filter Size of air inlet opening (air intake from below)
Page 30
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 IDR3-X 140M/ IDR3-X 160M Return Air Inlet Air Outlet Size of Air Outlet Size of Return Air Inlet External dimension Size of Air Outlet Size of Return Air Inlet...
Page 31
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual 3. Wiring Diagrams IDR3-X 26M/ IDR3-X 35M/ IDR3-X 53M/ IDR3-X 71M...
Page 32
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 IDR3-X 90M...
Page 33
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual IDR3-X 105M...
Page 34
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 IDR3-X 140M / IDR3-X 160M...
Page 35
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual 4. Capacity Table Model 26 Cooling mode: Indoor air temperature (° C WB/DB) Indoor Outdoor air airflow rate temperature 14/20 16/23 18/26 19/27 20/28 22/30 24/32 (° C DB) 10.00...
Page 37
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Heating mode: Indoor air temperature (° C DB) Outdoor air temperature Indoor airflow (° C) rate (m -15.30 -15.00 2.53 2.36 2.19 2.11 2.02 1.85 -13.00 2.71 2.54 2.37 2.28...
Page 39
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Model 35 Cooling mode: Indoor air temperature (° C WB/DB) Indoor Outdoor air 14/20 16/23 18/26 19/27 20/28 22/30 24/32 airflow rate temperature (° C DB) 10.00 4.13 2.80 4.39...
Page 41
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Heating mode: Indoor air temperature (° C DB) Outdoor air temperature Indoor (° C) airflow rate -15.30 -15.00 2.64 2.45 2.26 2.17 2.08 1.89 -13.00 2.86 2.68 2.49 2.39 2.30...
Page 43
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Model 53 Cooling mode: Indoor air temperature (° C WB/DB) Outdoor air Indoor airflow 14/20 16/23 18/26 19/27 20/28 22/30 24/32 temperature rate (m (° C DB) 10.00 7.21 4.58...
Page 45
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Heating mode: Indoor air temperature (° C DB) Indoor airflow Outdoor air temperature (° C) rate (m -15.30 -15.00 3.48 3.26 3.04 2.95 2.87 2.69 -13.00 -12.60 3.88 3.66 3.45...
Page 47
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Model 71 Cooling mode: Indoor air temperature (° C WB/DB) Indoor Outdoor air 14/20 16/23 18/26 19/27 20/28 22/30 24/32 airflow rate temperature (° C DB) 10.00 10.28 6.35 10.55...
Page 49
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Heating mode: Indoor air temperature (° C DB) Indoor airflow rate Outdoor air temperature (° C) -15.30 6.34 6.12 5.89 5.81 5.72 5.54 -15.00 -13.00 6.74 6.52 6.29 6.21 6.12...
Page 51
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Model 90 Cooling mode: Indoor air temperature (°C WB/DB) Indoor Outdoor air airflow 14/20 16/23 18/26 19/27 20/28 22/30 24/32 temperature rate (°C DB) 10.00 10.38 7.13 10.86 7.28 11.34...
Page 53
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Heating mode: Indoor air temperature (° C DB) Outdoor air Indoor airflow rate (m temperature (° C) -15.30 -15.00 5.46 5.20 4.94 4.81 4.68 4.42 -13.00 6.01 5.75 5.49 5.36...
Page 55
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Model 105 Cooling mode: Indoor air temperature (° C WB/DB) Indoor Outdoor air 14/20 16/23 18/26 19/27 20/28 22/30 24/32 Airflow temperature m3/h (° C DB) 10.00 12.80 8.28 13.10...
Page 57
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Heating mode: Indoor air temperature (° C DB) Outdoor air Indoor Airflow temperature (° C) m3/h -15.30 -15.00 6.74 6.42 6.10 5.95 5.80 5.50 -13.00 -12.60 7.34 7.02 6.70 6.55...
Page 59
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Model 140 Cooling mode: Indoor air temperature (° C WB/DB) Indoor Outdoor air airflow 14/20 16/23 18/26 19/27 20/28 22/30 24/32 temperature rate (° C DB) 10.00 16.80 10.86 17.10...
Page 61
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Heating mode: Indoor air temperature (° C DB) Outdoor air temperature Indoor airflow (° C) rate (m -15.30 -15.00 10.92 10.60 10.28 10.13 9.98 9.68 -13.00 -12.60 11.54 11.22 10.90...
Page 63
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Model 160 Cooling mode: Indoor air temperature (° C WB/DB) Indoor Outdoor air airflow 14/20 16/23 18/26 19/27 20/28 22/30 24/32 temperature rate (° C DB) 10.00 19.55 12.64 19.85...
Page 65
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Heating mode: Indoor air temperature (° C DB) Outdoor air temperature Indoor airflow rate (° C) -15.30 -15.00 12.74 12.40 12.06 11.90 11.74 11.42 -13.00 -12.60 13.39 13.05 12.71 12.55...
Page 67
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual 5. Static Pressure Curve Model 26 Airflow(m3/h) Model 35 Airflow(m3/h)
Page 68
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 Model 53 1000 Airflow(m3/h) Model 71 1000 1100 1200 1300 1400 Airflow(m3/h)
Page 69
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Model 90 1000 1100 1200 1300 1400 1500 1600 Airflow(m3/h) Model 105 1200 1400 1600 1800 2000 2200 2400 Airflow(m3/h)
Page 70
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 Model 140 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 Airflow(m3/h) Model 160 1500 1700 1900 2100 2300 2500 2700 2900 3100 3300 Airflow(m3/h)
Page 71
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual 6. Electric Characteristics Power supply Indoor fan motors Rated Model name Min. Max. Volts motor volts volts output (kW) IDR3-X 26M 0.425 0.03 0.34 50/60 220-240 IDR3-X 35M 0.45 0.03...
Page 72
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 7. Sound Levels Model Noise level under three speeds of fan (dB(A)) MCR3-X 26M 34/33/19 MCR3-X 35M 35/34/21 MCR3-X 53M 36/35/24 MCR3-X 71M 38/32/29 MCR3-X 90M 43/39/36 MCR3-X 105M...
Page 73
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual 8. Accessories Accessory name of indoor unit Qty. Purpose Installation Manual Installation instructions User Manual Operating Instructions of air conditioner For use in the installation of connecting pipe (the quantity is one...
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 Part. 4 Installation & Troubleshooting 1. Notes ................78 2. Installation of Duct Type Indoor Units ......75 3. Installation of Outdoor Units .......... 78 4. Water discharge piping layout ........83 5.
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual 1. Notes 1.1 Selecting an installation site for IDU • Enough space for installation and maintenance. • The ceiling is level, and the structure is strong enough to support the weight of IDU; take reinforcement measures when necessary.
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 2. Installation of Duct Type Indoor Units 2.1 Installating space Ensure enough space required for installation and maintenance. (Unit: mm) 2.2 Mount the unit • Use the Φ10 lifting bolts (four).
Page 77
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual 2.3 Lifting the IDU • Mount the lifting bolt in the U-shaped groove to install the lifting lugs, lift the machine, and use the gradienter to determine how level the device is.
Page 78
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 Air inlet grille Air inlet direction Air inlet grille Air inlet direction Figure 2 Figure 1 You need to add sponges to the air outlet flange for insulation. Metallic air diffuser Figure 3 2.5 Steps to dismantle the drain pan...
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual 3. Installation of Outdoor Units 3.1 Installating space Ensure enough space required for installation and maintenance. (Unit: mm) (Wall or obstacle) Maintenance cable and Air inlet surface >300 pipeline surface >300...
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 4. Water discharge piping layout Note: Do not exert too much force when installing the suction piping in order not to break the pipes. Wrap both the suction piping and water discharge piping evenly with heat insulation protective casing to prevent water condensation.
Page 81
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual 4.2 Water discharge test 1.Before the test, make sure that the water discharge pipeline is smooth, and check that each connection is sealed properly. 2.Conduct the water discharge test in the new room before the ceiling is paved.
Page 82
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 5. Connection of Connecting Pipe 5.1 Length and level difference requirements for the pipe connections of IDU and Product Model Maximum length(m) Maximum level difference(m) Maximum number of bends(m)
Page 83
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual than 3.5D (pipe diameter). • Do not bend the flexible tube back and forth more than 3 times. Bend a thin-walled connecting pipe (see the figure below): • When bending a pipe, cut off the required recess in the insulation pipe at the bend and expose the pipe (wrap the bend with a binding tie after bending).
Page 84
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 5.4 Pipe connection Flaring Use a pipe cutter to cut off the pipe, and rotate the pipe cutter repeatedly to cut off the pipe. Insert the pipe into the connection nut flare.
Page 85
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Manifold valve Multimeter Pressure gauge -755mmHg Hi handle Lo handle Charging hose Charging hose Vacuum pump Low pressure valve Adding Refrigerant • If the one-way pipe length is less than 5m (including 5m), the refrigerant charging amount is determined according to the nameplate.
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 6. Electric Connection 6.1 Caution Before the installation, check whether the power supply of the user meets the electrical installation requirements of the product (including reliable grounding, power leakage, and wire-diameter electrical load).
Page 87
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual 6.3 Schematic diagram 26/35/53/71 Power supply Main switch/fuse (can be purchased locally) Power cable of indoor unit Grounding Grounding Indoor and outdoor power cable 90/105/140/160 Single-phase ODU electrical control system connection diagram (IDU and ODU use separate power...
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 7. Duct Design Scheme Examples of construction and ventilation pipeline design scheme (Flowering hidden series.) Construction and ventilation pipeline design scheme...
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual 8. Trial Run 1. Conduct the test run only after all installation tasks have been completed. 2. Check the following items during the test run. Indoor and outdoor units are properly installed.
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 9. Trouble shooting 9.1 Fault information and codes 1. Error code table(Indoor unit display) 26/35/53/71 Error code Error definition Error display IDU EPROM fault Immediate display, spot check available...
Page 91
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual protection Outdoor electric control current protection Immediate display, spot check available IDU current protection Immediate display, spot check available ODU current protection Immediate display, spot check available Input AC current sampling circuit fault...
Page 92
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 Error code Error definition Error display IDU mismatching error Immediate display, spot check available L (L0/L1) error occurs three times in one hour, reporting H4,and this error is not recoverable.
Page 93
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Protection for a difference of > 15Hz between Display after 10 minutes, spot check available the set speed and operating speed Detected DC bus voltage (PN voltage) < Display after 10 minutes, spot check available...
Page 94
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 105/140/160 Error code Error definition Error display IDU mismatching error Immediate display, spot check available L (L0/L1) error occurs three times in one hour, reporting H4,and this error is not recoverable.
Page 95
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual Protection for a difference of > 15Hz between Display after 10 minutes, spot check available the set speed and operating speed Detected DC bus voltage (PN voltage) < Display after 10 minutes, spot check available...
Page 96
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 2. Spot check query function (Press the button on the display board to spot check the system parameters) 26/35/53/71 Sequence number Spot check parameter contents Remarks Actual value, temperature accurate to 0.5 ℃...
Page 97
MCAC-UTSM-202006 Midea LC3 Series DC Inverter Air conditioner Technical Service Manual 90/105/140/160 Sequence Spot check parameter contents Remarks number 0:Standby;1:Fan only;2:Cooling;3:Heating;4:Forced Operating mode Cooling;6:dehumidification Operating wind speed and level 0:OFF;1:Low speed;2:Middle speed;3:High speed The capacity of Indoor unit(HP) The total capacity demand of...
Page 98
Midea LC3 Series DC Inverter Air conditioner Technical Service Manual MCAC-UTSM-202006 9.2 Fault and troubleshooting Fault Cause Solution Starting Power failure Wait for the power supply to be failure restored. Power switch is off Turn on the power The fuse of the power switch is blown.