Continental Girbau CG75-85 Installation Manual page 62

Gas dsi/electric/steam
Hide thumbs Also See for CG75-85:
Table of Contents

Advertisement

e. Open main door. The dryer must stop and ALL indicator lights on the back side of the microprocessor
controller (computer) board must go out. (Refer to the illustration on the previous page.)
f. Try to restart the dryer with the main door open.
g. The microprocessor controller (computer) board's light emitting diode (L.E.D.) display must read "DOOR."
h. Close the main door and restart the dryer.
i. Functional check of microprocessor controller (computer) board is complete.
2. For Models With Johnson Controls Direct Spark Ignition (DSI) Module (G760)
Theory Of Operation:
Start the drying cycle. When the gas
burner ignites within the chosen trial for
ignition time (6-seconds), the flame sensor
detects gas burner flame and signals the
DSI module to keep the gas valve
open...as long as there is a call for heat.
The DSI module will "LOCKOUT" if
the gas burner flame is not sensed at the
end of the trial for ignition period. The
trial for ignition period will be repeated
for a total of three (3) retries/trials (the
initial try and two [2] more retries/trials).
If the flame is not sensed at the end of
the third retry/trial (inter-purge period of
30-seconds) the DSI module will
"LOCKOUT" (L.E.D. flashes).
A steady L.E.D. indicator indicates
normal operation.
No L.E.D. indicator indicates a power or
an internal failure has occurred.
58