Continental Girbau CG75-85 Installation Manual page 29

Gas dsi/electric/steam
Hide thumbs Also See for CG75-85:
Table of Contents

Advertisement

CG75-85 (Gas/Steam)
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
208 VAC AND 240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.
NOTES:
A.
When fuses are used they must be dual element, time delay,
current limiting, class RK1 or RK5 ONLY. Calculate/determine
correct fuse value, by applying either local and/or National
Electrical Codes to listed appliance amp draw data.
B.
Circuit breakers are thermal-magnetic (industrial) motor curve type
ONLY. For others, calculate/verify correct breaker size according
to appliance amp draw rating and type of breaker used.
C.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.
SERVICE
PHASE
VOLTAGE
120
208
240
208
240
380-400
416
460-480
* 380, 400, 416 volt dryers are built (4-wire) only. Customer must contact factory to special order 3-wire systems.
IMPORTANT: Figures shown are for non-reversing models only. For reversing models contact
Continental Girbau, Inc.
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is
affixed to the left side panel area behind the top control (access) door. In the case of
208 VAC or 240 VAC, the supply voltage must match the electric service
specifications of the data label exactly.
IMPORTANT: The wire size must be properly sized to handle the related current.
WARNING: 208 VAC AND 240 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: The manufacturer reserves the right to make changes in specifications at any time without
notice or obligation.
WIRE
SERVICE
2
2
2
3
3
4*
4*
3
®
25
APPROX.
AMP DRAW
60 Hz
50 Hz
13
---
7.6
---
7.0
7.8
4.7
---
4.9
5.7
---
3.0
---
3.1
2.8
---
CIRCUIT
BREAKER
20
15
15
15
15
15
15
15
041403