7.3

ALARMS

The ALARMS mode is entered any time the "ALARM" key is pressed.
The LCD will display a series of screens corresponding to the last 255 events, two events per screen
(LEVEL 1
USER).
In this mode the keys perform the following functions:
Return to HOME screen.
Scrolls backward to the previous screen.
Scrolls forward to the next screen.
Move forward to the following event.
Move back to the following previous event.
Confirm the selection made.
It is possible to view any key functional description by pushing the key for more than 3 seconds.
The events displayed are the standard GE events as described in the Section 7.3.1 - EVENTS (Alarms
and Messages).
Home\ Alarm
ALARM
LEVEL 1
:
LEVEL 2
:
Home\Alarm\User
NR =
255
03.03.2009
C
=
4404
K6 CLOSING FAILURE
S
=
00008180
NR =
254
01.03.2009
C
=
4583
COMMAND TO SYNCHRONIZE
S
=
00008180
Modifications reserved
OPM_LPS_33E_60K_M12_2GB_V010.doc
Alarms screen
LEVEL 1
Chronologically view 2 events per screenshot.
USER
SERVICE
LEVEL 2
Chronologically view 5 events per screenshot with service
related info.
Screen of user alarms
15.37.25
NR
12.45.57
C
S
USER
SERVICE
Number chronologically assigned to an event (Nr.
255 is the more recent, Nr. 1 is the first).
Date and exact hour of the moment when the event
occurred.
Number of standard GE code of the event and an
explicit text describing the event in the selected
languages.
Status code of the UPS.