Advertisement

Example 5:
An equivalent set of parameters for Example 4 is.
Weekday
d1
ECO Mode START
00:00
ECO Mode STOP
23:59
ECO Mode START
ECO Mode STOP
The ECO Mode is active from 18:00 of weekday d3 - Monday until 06:00 of weekday d4 - Tuesday (as
indicated by the ECO Mode STOP time of weekday d4 - Tuesday).
The ECO Mode STOP time of weekday d3 - Monday has no effect as it is followed by the ECO Mode STOP
time of weekday d4 - Tuesday.
It can be, without change of meaning, any time between 18:00 and 23:59.
Similarly, the ECO Mode is active from 18:00 of weekday d4 - Tuesday until 06:00 of weekday d5 -
Wednesday.
The ECO Mode START time of weekday d5 - Wednesday has no effect as it is preceded by the ECO Mode
START time of weekday d4 - Tuesday.
It can be, without change of meaning, any time between 00:00 and 06:00.
NOTE !
To avoid undesired ECO Mode operation, verify:
• Date and Time (first page of parameter).
• ECO mode screen how many hours of ECO Mode operation have been selected for
each day of the week.
NOTE !
The ECO Mode will become active only if the load is supplied from the inverter.
Modifications reserved
OPM_LPS_33E_60K_M12_2GB_V010.doc
d2
d3
- Saturday
- Sunday
00:00
20:00
d4
d5
- Monday
- Tuesday
18:00
18:00
18:00
06:00
d6
- Wednesday
- Thursday
06:00
09:00
06:00
09:00
Operating Manual LP 33 Series 60-80-100-120 kVA / S2
d7
- Friday
12:00
13:00
Page 68/103