DESCRIPTION

4.1

PRINCIPAL DIAGRAM AND MAIN ELEMENTS DESCRIPTION

The Uninterruptible Power Supply System LP 33 Series can be divided into the following main elements:
Electronics
The UPS is designed with a microprocessor–controlled supervision and diagnostic system.
Communication between user and UPS is achieved by the front panel consisting of an LCD screen,
displaying the operation modes, the measurements and the events / alarms.
Rectifier – Active IGBT Rectifier
The Active IGBT Rectifier converts the 3-phase mains voltage into a controlled and regulated DC-voltage,
supplying the inverter and to charge the battery through the battery-charger.
Thanks to modulation strategy applied to IGBT bridge, the rectifier provides clean input power in terms
of low THDi and unity power factor. For this purpose the UPS's are offered in two configurations
depending on the required harmonic content (THDi): - Active IGBT Rectifier
Both configurations provide clean input current at full and partial loads, avoiding thus possible
interference with other upstream equipment.
Inverter
The inverter converts the DC voltage into a three-phase sinusoidal with constant amplitude and
frequency, which is completely independent from the AC-input voltage.
Automatic Bypass
The automatic bypass consists of a static semiconductor-switch (SSR: Static Switch Relay), used to
provide an uninterrupted transfer of the load from inverter to mains when operating in VFI (Voltage
Frequency Independent) Mode.
If chosen the ECO Mode, the SSM transfer the load from mains to inverter in case the utility fails.
Back-Feed Protection
All LP 33 Series UPS's are equipped with an automatic system for the protection against voltage back
feeding towards Utility, through the Bypass (Applied Standard IEC 62040-1).
This protection works automatically by opening contactor K6 (in series with the thyristors of the static
switch) and eventually K7, and acts in case of internal defects of the system, or due to wrong
manipulations on the maintenance bypass Q2.
Manual Bypass
The manual bypass consists of a pair of manual switches Q1 and Q2, which allow the isolation of the
UPS from the load, while still supplying the load with power directly from the mains.
Battery
The battery, normally stored by the battery-charger, supplies the DC energy to inverter in the event of
mains failure.
Modifications reserved
OPM_LPS_33E_60K_M12_2GB_V010.doc
Fig. 4.1-1 UPS principal diagram
- Active IGBT Rectifier - Clean Input Module
Page 14/103
Operating Manual LP 33 Series 60-80-100-120 kVA / S2