During the first commissioning LP 33 Series requests a set up of the UPS configuration parameters
presented in the following screens.
Without such configuration it is not possible to continue with the commissioning procedure.
WARNING !
The setup of the UPS configuration parameters must be done only by QUALIFIED
AND TRAINED PERSONNEL.
The setup of mistaken values could compromise the integrity and reliability of the
UPS.
In this mode the keys perform the following functions:
Confirm the selection made and select the next parameter.
ESC
Re-establish default value.
Modify or insert the selected value.
Save the configuration of set parameters.
Configuration
DISPLAY CONFIGURATION
Select language
ESC
Configuration
UPS CONFIGURATION
Input frequency
Output frequency
Inverter voltage
ESC
Modifications reserved
OPM_LPS_33E_60K_M12_2GB_V010.doc
DISPLAY CONFIGURATION screen
Select language
:
ENGLISH
This parameter allows the choice of language used to display
the information.
UPS CONFIGURATION screen
Input frequency
:
50
Hz
Input frequency value (*50Hz).
:
50 Hz
Output frequency
:
230
V
Inverter output frequency value (*50Hz).
Inverter voltage
Output voltage PHASE/NEUTRAL of the inverter (220V/230V/240V).
*) Configuration of the frequency to 60Hz requires the
intervention of a Service Centre.
Continue ►
Page 71/103
Operating Manual LP 33 Series 60-80-100-120 kVA / S2