GE LP 33 Series Operating Manual page 51

60 – 80 – 100 – 120 kva 400 vac ce / series 2
Hide thumbs Also See for LP 33 Series:
Table of Contents

Advertisement

LED Stop Operation (red colour)
It warns about the imminent inverter stop (default parameter = 3 min.) and the
consequent load shutdown as result of:
LED Alarm (yellow colour)
It blinks when one or more alarm is activated. The internal buzzer is ON.
The LED remains
when the key "MUTE" is pressed.
LED Alarm is lit when the load is not protected by UPS or in case Q1 is open.
LED Operation (green colour)
When lit, indicates that the UPS is functioning correctly and the load is system
protected (Load supplied either from inverter or from Automatic Bypass in case of
ECO Mode functionality).
When blinking, indicates that a regular maintenance service is needed (SERVICE
REQUIRED).
May be reset by a service technician only.
See Section 11 – Maintenance – Service check.
The LED is OFF when the output switch Q1 is open, indicating that the Inverter is in
service mode, not supplying the load.
Modifications reserved
OPM_LPS_33E_60K_M12_2GB_V010.doc
The battery is fully discharged and the load cannot be transferred on mains.
Overtemperature or overload condition (>125%) and the load cannot be
transferred on mains.
(with the alarm condition still present) and the buzzer stops
lighted
User LCD Interface
The user interface consists of a Back lit Graphic
Display (LCD) having:
Synoptic diagram indicating UPS status.
UPS
operating,
information.
History of events (alarms and messages).
Functionality can be programmed to meet
customer needs by changing parameters.
Operation commands of the UPS.
Operating Manual LP 33 Series 60-80-100-120 kVA / S2
AC
and
DC
metering
Page 51/103