Sunny Boy Sb 8000-Us (Sb 8000Us And Sb 8000Us-12) - SMA SUNNY BOY 5000-US Installation Manual

Pv inverter
Hide thumbs Also See for SUNNY BOY 5000-US:
Table of Contents

Advertisement

SMA America, LLC

11.4 Sunny Boy SB 8000-US (SB 8000US and SB 8000US-12)

PV Array Connection
Maximum MPP voltage
Nominal operating voltage
Range of input operating voltage
Maximum generator input power
Maximum DC power
PV start voltage
Maximum DC input current
Maximum input short-circuit current
Maximum utility backfeed current to PV array
DC voltage ripple
Grid Connection
AC operating voltage range at 240 V nominal value
AC operating voltage range at 277 V nominal value
AC operating frequency range
AC frequency, nominal value
AC maximum continuous output power at 240 V
AC maximum continuous output power at 277 V
Current THD
Maximum continuous AC output current at 240 V
Maximum continuous AC output current at 277 V
Maximum output failure current
Maximum output overcurrent protection
Synchronization of inrush current
Trip limit accuracy
Trip time accuracy
Power consumption at night
General Data
Inverter technology
Cooling concept
SB50US-80US-IA-en-36
300 V ... 480 V
345 V
300 V ... 600 V
10 000 W
8 600 W
365 V
30 A
36 A
50 A AC
< 10 %
211 V ... 264 V
244 V ... 305 V
59.3 Hz ... 60.5 Hz
60 Hz
7 680 W
8 000 W
< 4 %
32 A
29 A
61.7 A
50 A
14.32 A
±2 %
±0.1 %
0.1 W
True sine, low-frequency transformer
OptiCool
SB50US-80US-IA-en-36
Technical Data
97

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunny boy 6000-usSunny boy 7000-us

Table of Contents