SMA America, LLC
Name
Operating Mode
V-Const Setval
Vac-Min*
Vac-Max*
Vac-Min-Fast*
Vac-Max-Fast*
Vac-Min-Recnet
Vac-Max-Recnet
SB50US-80US-IA-en-36
Unit
Range
MPP-Operation,
Turbine, V-const,
Stop
SB 5000-US -
G
SB 7000-US:
250 ... 600
SB 8000-US:
300 ... 600
%
0 ... 50
%
0 ... 20
%
0 ... 50
%
0 ... 20
%
0 ... 50
%
0 ... 20
Standard
Password
Level
MPP
Electrically
qualified
person
600
Electrically
qualified
person
12
Electrically
qualified
person
10
Electrically
qualified
person
50
Electrically
qualified
person
20
Electrically
qualified
person
11.7
Electrically
qualified
person
5.83
Electrically
qualified
person
Displays and Messages
Description
Operating modes of the Sunny Boy:
MPP-Operation: Sets the Sunny Boy
in Maximum Power Point Tracking
Mode
V-const: Constant Voltage Mode
(target value defined in "Vconst-
Setval")
Turbine: Operating mode for wind
turbine systems
Stop: Disconnection from grid, no
operation
PV target voltage for constant
voltage operation. These
parameters only are important in the
event that the parameter "Operating
Mode" is set to "V-const".
Values are used to calculate the
lower limit of permissible AC
voltage.
Standard value is optimal for plants
< 30 kW. Standard value 12 results
in a trip value of 88 %, as the list of
trip limits shows.
Values are used to calculate the
upper limit of permissible AC
voltage.
Standard value is optimal for plants
< 30 kW. Standard value 10 results
in a trip value of 110 %, as the list of
trip limits shows.
Values are used to calculate the
lower limit of allowable AC voltage
for fast disconnection. Standard
value is optimal for plants < 30 kW.
Standard value 50 results in a trip
value of 50 %, as the list of trip limits
shows.
Values are used to calculate the
upper limit of allowable AC voltage
for fast disconnection. Standard
value is optimal for plants < 30 kW.
Standard value 20 results in a trip
value of 120 %, as the list of trip
limits shows.
Values are used to calculate the
lower and upper limits to reconnect
to the grid after a grid failure.
SB50US-80US-IA-en-36
75