Displays and Messages
Name
Default
dFac-MAX*
E_total
Fac-delta–*
Fac-delta+*
Fac-MinTripTime*
Fan-Test
h_Total
Memory Function
74
SB50US-80US-IA-en-36
Unit
Range
USA/UL1741/
2005, OFF_Grid,
NON IEEE1547
Hz/s
0.005 ... 4
kWh
0 ... 200000
Hz
0.2 ... 3
Hz
0 ... 4.5
s
0.16 ... 300
1 / 0
h
0 ... 200000
no function, Default
param., Reset
Op.Data, Reset
errors
Standard
Password
Level
USA/
Electrically
UL1741/
qualified
2005
person
0.5 (for
Electrically
country setting
qualified
USA/
person
UL1741/
2005)
0
Electrically
qualified
person
0.69 (for
Electrically
country setting
qualified
USA/
person
UL1741/
2005)
0.49 (for
Electrically
country setting
qualified
USA/
person
UL1741/
2005)
0.16
Electrically
qualified
person
0
Electrically
qualified
person
0
Electrically
qualified
person
no function
Electrically
qualified
person
SMA America, LLC
Description
Used for adjusting the country
specific parameter settings.
Note: After changing one of the
parameters marked with "*", the
parameter "default" changes to
"adjusted" automatically.
Maximum "number of frequency
changes" before the anti-islanding
protection switches on
Total energy yield of the inverter.
Changing the value may be
necessary if a Sunny Boy is replaced
and you wish to compare the data
obtained previously.
Maximum permissible operating
frequency above and below 60 Hz.
Standard value is optimal for plants
< 30 kW.
Switch-off time having fallen below
power frequency. The standard
value is optimal for plants < 30 kW.
By setting this parameter to "1" you
can check the function of the fans.
This test turns the fans at maximum
speed.
Total operating hours of the inverter.
Changing the value may be
necessary if a Sunny Boy is replaced
and you wish to compare the data
obtained previously.
Default param.: Sets all parameters
to the standard value.
Reset Op.Data: Sets all parameters
to the standard values that are
displayed on the user level.
Reset errors: Resets all permanent
errors that lead to device
disconnection.