Programming the Panel
Fire Report Delay
Default = 0 Minutes
This setting allows you to specify the length of time (in minutes)
between the time a fire alarm condition is detected, and a report is
sent to the central station. This allows users time to cancel the
report of a false alarm if setting xx089 is on.
Specifying the Fire Report Delay:
Once the item number has been entered, enter the number of min-
utes (0–15) you wish the panel to wait before sending a report.
Press # to apply the new setting.
Second Fire Alarm Ends Reporting Delay
Default = 1 (On)
If on, and a fire report delay is in progress, a second fire alarm
condition will end the fire report delay (xx014) immediately send-
ing a report to the central station.
Programming Second Fire Alarm Ends Reporting Delay:
Once the item number has been entered, enter 1 to turn the setting
on (second alarm ends delay) or 0 to turn it off. Press # to apply
the new setting.
Second Intrusion Causes Report
Default = 0 (Off)
If on, the first trip of an intrusion zone causes a local police alarm.
A second trip (different intrusion zone) within four minutes gen-
erates a report. If off, the first trip of an intrusion zone generates
both an alarm and report.
Setting Second Intrusion Causes Report:
Once the item number has been entered, enter 1 to turn the setting
on or 0 to turn it off. Press # to apply the new setting.
All Restoral Reports
Default = 0 (Off)
If on, restoral reports are generated for all reporting zone types
(which require restoral). If off, the zone type definition dictates
whether on not a restoral report is generated.
Turning All Restoral Reports On/Off:
Once the item number has been entered, enter 1 to turn the setting
on or 0 to turn it off. Press # to apply the new setting.
Local Closing Report Verification
Default = 0 (Off)
When on, the panel will locally verify that a closing report has
been sent to the central station with an audible signal.
Note
In order for this setting to work, Exterior Siren Verifica-
tion setting (xx097) must be set to "on."
To Turn Local Closing Report Verification On/Off:
Once the item number has been entered, enter 1 to turn the setting
on or 0 to turn it off. Press # to apply the new setting.
20
Arming Settings
xx014
Enable Level 2 Arming
Enable Level 3 Arming
Enable Level 4 Arming
Enable Level 5 Arming
Defaults = 1 (On)
If on, the selected arming level will be enabled (level 1 is always
enabled) in the selected partition/area. Users will then have access
to this arming level. An arming level is the degree of security pro-
tection set at the panel.
To Enable Arming Level:
Once the item number has been entered, enter 1 to turn the setting
on (level enabled) or 0 to turn it off. Press # to apply the new set-
ting.
xx090
Default Keyfob/Schedule Arming Level
Default = 3
This setting allows you to select the arming level (2–5) the panel
arms to when armed by a keyfob or schedule (auto arming).
Specifying Keyfob/Schedule Arming Levels:
Once the item number has been entered, enter the keyfob/sched-
uled arming level (2–5). Press # to apply the new setting.
xx077
Default Keyswitch Arming Level
Default = 3
This setting allows you to select the arming level (2–5) the panel
arms to when armed by a keyswitch.
Specifying Keyswitch Arming Levels:
Once the item number has been entered, enter the keyswitch arm-
ing level (2–5). Press # to apply the new setting.
Activity Fault Threshold 1
xx112
Activity Fault Threshold 2
Activity Fault Threshold 3
Defaults:
Threshold 1 = 10, Threshold 2 = 30, Threshold = 50
This setting allows you to specify the number of disarms without
any activity before zone activity trouble is generated.
Specifying Activity Fault Thresholds:
Once the item number has been entered, enter the number of dis-
arms before zone activity trouble is generated (2–255). Press # to
apply the new setting.
xx098
Enable Scheduled Arming
Default = 1 (On)
This setting allows you to select whether or not to allow the sys-
tem to arm/disarm according to a schedule.
Turning Enable Scheduled Arming On/Off:
Once the item number has been entered, enter 1 to enable sched-
uled arming or 0 to turn it off. Press # to apply the new setting.
Commercial Burglary and Home Navigator System
xx025
xx026
xx027
xx028
xx118
xx120
xx018
xx019
xx020
xx094