This decision specifies the amount of time that will be allowed to elapse between alarm retries. Retries occur
when an alarm is not acknowledged by a network alarm acknowledger, which may be either a Building
Supervisor, an Autodial Gateway, or a Dataport 2. If the acknowledgement is not received, the alarm will be
retransmitted after the number of minutes specified in this decision.
Allowable Entries
Default
REALARM TIME
This decision specifies the amount of time that will be allowed to elapse between re-alarms. A re-alarm
occurs when the condition that caused the initial alarm continues to persist for the number of minutes
specified in this decision. Re-alarming will continue to occur at the specified interval until the condition
causing the alarm is corrected.
Allowable Entries
Default
ALARM SYSTEM NAME
This decision specifies the system element name that will appear in alarms generated by the Pro-Dialog
control.
Allowable Entries
Default
Downloaded from
www.Manualslib.com
CARRIER SA
30GX&HX PRO_DIALOG 4 V.2
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
manuals search engine
USER'S GUIDE FOR
1 to 240 minutes
10 minutes
1 to 254 minutes
30 minutes
Up to 8 alphanumeric characters
PRO_30GX
C
©
.
ARRIER S
A
ECG - UG - 02 - 02
Page: 34 /98
Rev: Original