2.2. Set the station No. and baud rate

For the setting station number or communication speed to take effect, power needs to be
turned off and then turned back on.
Set the Station No.
The station number can be set between 1 and 64.
The switch x10 is set up the ten's place and x1 is set up the ones.
Set the arrow (↑) of the corresponding switch to the required numeral.
Set the transmission speed. (For details, refer to the CC-Link master unit manual.)
Transmission Speed
It causes an error when the switches are not set correct position (ex. set position between 0
*
and 1 switch label), or set over 5.

2.3. About indicator of LED

The LED shows the present status of the network and error.
C
C
I
L
i
n
k
■Layout of LED
x10
x1
Setting Switch
156kbps
Power
Light on during transmission period.
L.RUN
Light on during communication.
SD
Light on during send the data of CC-Link.
Light on during receive the data of
RD
CC-Link
L.ERR
Light on during communication error
POWER
2.1
L.RUN
2.2
SD
2.3
RD
2.4
L.ERR
2.5
BAUD RATE
0
1
625kbps
2.5Mbps
- 7 -
E6581286②
2
3
5Mbps
4
10Mbps