10. Installation Instruction

10.1 Select The Best Location

10.1.1 Indoor Unit
Do not install the unit in excessive oil fume area such as kitchen, workshop and etc.
There should not be any heat source or steam near the unit.
There should not be any obstacles blocking the air circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
Recommended installation height for indoor unit shall be at least 2.5m.
10.1.2 Outdoor Unit
If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
There should not be any animal or plant which could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
Do not place any obstacles which may cause a short circuit of the discharged air.
If piping length is over the rated length, additional refrigerant should be added as shown in the table below:
Model
Horse
Power
S9***
S10***
1.0 ~
S12***
1.75HP
S13***
S15***
S18***
2.0 ~
S24***
2.5HP
10.1.3 Indoor/Outdoor Unit Installation Diagram
Piping direction
Attention not to bend
up drain hose
(Front side)
Right
Right
Rear
Left
Right bottom Left
Rear
Left bottom
Length of power supply cord
About
About
960 mm
1660 mm
• This illustration is for explanation purposes onl y .
The indoor unit will actually face a different way.
Insulation of piping connections
• Carry out insulation after
checking for gas leaks and
secure with vinyl tape.
* Vinyl Tape
Attaching the remote control holder to
the wall
Remote control holder
Remote
control
Piping size
Rated Length
(m)
Gas
Liquid
3/8"
1/4"
7.5
3/8"
1/4"
7.5
1/2"
1/4"
7.5
1/2"
1/4"
7.5
1/2"
1/4"
7.5
1/2"
1/4"
5/8"
1/4"
50mm
or more
It is advisible to avoid more than 2 blockage directions.
Remote
control
holder
Max Elevation
Min Piping
(m)
Length (m)
5
5
5
5
5
5
15
5
15
19
Max Piping
Additional
Length (m)
Refrigerant
3
15
3
15
3
15
3
15
3
15
3
20
3
20
Installation parts you
should purchase (*)
Installation plate
Brushing-Sleeve (*)
Sleeve (*)
Putty (*) (Gum type Sealer)
Bend the pipe as closely on the wall as possible,
but be careful that it doesn't break.
Vinyl tape (wide) (*)
• Apply after carrying out a drainage test.
• To carry out the drainage test, remove the air
filters and pour water into the heat exchanger
Saddle (*)
Connecting cable
Liquid side piping (*)
Gas side piping (*)
Additional drain hose
Piping length
for add. gas
(g/m)
(m)
15
7.5
15
7.5
15
7.5
15
7.5
15
7.5
15
10
20
10