Installation Of Unit - LG AMNH096BTG0 Manuals

Multi type air conditioner
Hide thumbs Also See for AMNH096BTG0:
Table of Contents

Advertisement

Installation
- B1, B2 Chassis

Installation of Unit

Install the unit above the ceiling correctly.
CASE 1
POSITION OF SUSPENSION BOLT
• Apply a joint-canvas between the unit and duct to absorb
unnecessary vibration.
• Apply a filter Accessory at air return hole.
Dimension
A
B
C
Capacity
9/12k BTU/h 850
900
383
18/24k BTU/h 1130 1180 383
CASE 2
• Install the unit leaning to a drainage hole side as a figure
for easy water drainage.
POSITION OF CONSOLE BOLT
• A place where the unit will be leveled and that can support
the weight of the unit.
• A place where the unit can withstand its vibration.
• A place where service can be easily performed.
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
(Unit:mm)
D
E
F
G
H
570
93.5 190 20.6
795
163
570
93.5 190 20.6 1065 163
I
- 44 -
B
A
H
Drainage hole
M10 Nut
X 4
(Local
M10 SP. washer
X 4
supply)
M10 washer
X 4
M10 washer
X 4
(Local
M10 SP. washer
X 4
supply)
M10 Nut
X 4
LGE Internal Use Only

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents