3. Art Cool Deluxe Type Indoor unit
• Do not have any heat or steam near the unit.
• Select a place where there are no obstacles in front of the
unit.
• Make sure that condensation drainage can be conveniently
routed away.
Do not install near a doorway.
• Ensure that the space around the left and right of the unit is
more than 20cm. The unit should be installed as high on the
wall as possible, allowing a minimum of 30cm from ceiling.
• Use a stud finder to locate studs to prevent unnecessary
damage to the wall.
4. Duct Type Indoor Unit
Install the air conditioner in the location that satisfies the
following conditions.
• The place shall easily bear a load exceeding four times
the indoor unit's weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.(Suitable
dimension "H" is necessary to get a slope to drain as fig-
ure.)
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical
noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the
unit
5. CST Type Indoor Unit
• There should not be any heat source or steam near the
unit.
• There should not be any obstacles to the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into considera-
tion.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall,
ceiling, or other obstacles.
• The indoor unit must have the maintenance space
around.
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
More than 30cm
More than 2.3m
CAUTION
Install the indoor unit on the wall where the height
from the floors more than 2.3 meters.
Top view
(unit: mm)
600
Front view
Ceiling
Ceiling Board
50 or
more
- 35 -
Installation
More than 20cm
More than 30cm
Inspection hole
(600X600)
Control box
600
Front
H
Ceiling Board
50 or
more
Unit:cm
Floor
LGE Internal Use Only