12) Troubleshooting CH51, CH60
Display
Title
code
51
Over capacity
EEPROM
60
Check sum
Model
A2UW146FA0
A2UW146FA1
A2UW146FA2
A2UW166FA0
A2UW166FA1
A2UW186FA0
A3UW186FA0
A3UW246FA0
A4UW246FA0
A4UW306FA0
A6UW406FA0
Check Point
• CH 51
1. Check the indoor unit capacity.
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Cause of error
• Over capacity
Combination
• Check sum error
Gross max. capacity
21k
24k
30k
33k
39k
52k
- 207 -
Check point & Normal condition
• Check the indoor unit capacity.
• Check the combination table.
• Check the PCB ASM P/No.
• Check the poor soldering.
Max. single indoor unit capacity
12k
12K
18k
24K
24K
24K
• CH 60
1. Check the insertion condition of EEPROM.
2. Check the poor soldering
Troubleshooting Guide
LGE Internal Use Only