10. Concealed Floor-Standing Type (FM Type)
10-7. Indoor fan performance
How to Read the Diagram
The vertical axis is the EXTERNAL STATIC PRESSURE (mmAq) while the horizontal axis represents the AIR
FLOW (m
3
/minute). The characteristic curve for the "H", "Med", and "Lo" fan speed control.
The name plate values are shown based on the "H" air flow. Therefore in the case of the 25 type the flow is 17 m
minute, while the EXTERNAL STATIC PRESSURE is 1.5 mmAq at "H" position. If the external static pressure is too
great (due to long extention of duct, for example), the air flow volume may drop too low at each air outlet.
9 Type
3
2
1
0
5
Air Flow (m
18 Type
3
2
1
0
10
Air Flow (m
20
10
10
/minute)
3
0842_V_I
20
10
15
3
/minute)
0844_V_I
I - 131
ECO MULTI SYSTEM Unit Specifications
12 Type
3
2
1
0
5
Air Flow (m
25 Type
3
2
1
0
15
Air Flow (m
3
/
20
10
10
3
/minute)
0843_V_I
20
10
20
3
/minute)
0845_V_I
SM830052