Major Component Specifications - Sanyo SPW-C483GYH8 Service Manual

Eco multi system
Table of Contents

Advertisement

1. Outdoor Unit

1-2. Major component specifications

Outdoor Unit (A)
MODEL No.
Source
Controller P.C.B. Ass'y
Control circuit fuse
Compressor
Model ... Code No.
Nominal output
Compressor oil (SUNISO 4GSD-T) cc
Coil resistance
(Ambient temperature 25°C)
Safety devices
Thermal protector ON / OFF
Microprocessor safety devices
Crank case heater
High pressure switch
Set pressure
ON / OFF
Fan (Number ... diameter(mm))
Fan motor
Model ... Nominal output
No. of pole ... r.p.m. (230 V, High)
Coil resistance
(Ambient temperature 20 °C)
Safety device
Thermal protector ON / OFF
Run capacitor
Heat exchanger
Coil
Rows ... fin pitch
Face area
kW
°C
Compressor current detection circuit
Compressor discharge gas temperature control
Defective and negative phase detection circuit
Voltage drop detection circuit
V, W
2
kg/cm
W
°C
VAC , µF
mm
m
2
I - 9
ECO MULTI SYSTEM Unit Specifications
SPW – C483GYH8 / SPW – C483GY8
380 - 400 - 415 V / 3 phase / 50Hz
CR - C483GYH / CR - C483GY
250 V , 3.15 A
Rotary (Hermetic)
PC (Power Control)
C-5R433H8U ... 80843688
4.3
2,000
V - U: 2.76 , U - W: 2.59
W - V: 2.71
120 ± 5 / 98 ± 11
240, 32
ACB - 1TB07
24 ± 2.0 / 30
+ 2.0
+ 0.5
Propeller (2 ... ø 460)
KFC6T - 91C5P × 2 ... 70W × 2
6 ... 772 r.p.m.
BRN - WHT : 127.3
WHT - VLT :
VLT - YEL :
YEL - PNK :
130 ± 8 / 79 ± 15
440 V , 6 µF × 2
Aluminum plate fin / Copper tube
2 ... 2.0
1.08
56.7
15.0
7.2
SM830052
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents