Sanyo SPW-C483GYH8 Service Manual page 55

Eco multi system
Table of Contents

Advertisement

4. 1-Way Air Discharge Semi-concealed Type
Unit specifications (B)
MODEL No.
POWER SOURCE
PERFORMANCE
Capacity
Air circulation (Hi / Me / Lo)
Moisture removal (High)
ELECTRICAL RATINGS
Voltage rating
Available voltage range
Running amperes
Power input
Power factor
Fan motor locked rotor amperes
FEATURES
Controls / Temperature control
Timer
Fan speeds (Indoor unit)
Air filter
Refrigerant control
Operation sound (Hi / Me / Lo)
Refrigerant tubing connections
Refrigerant tube
diameter
Drain connection
Drain pump
Remote Controller
Refrigerant tubing kit / Accessories
DIMENSIONS & WEIGHT (include ceiling panel)
Dimensions
Net weight
Shipping weight
Shipping volume
Rated conditions
Cooling: Indoor air temperature 27 °C DB / 19 °C WB, Outdoor air temperature 35 °C DB
Heating: Indoor air temperature 20 °C DB
Indoor Unit
kW
BTU / h
3
m
/ h
Liters / h
V
V
A
W
%
A
dB-A
Narrow tube mm (in.)
Wide tube
mm (in.)
Height
mm (in.)
Width
mm (in.)
Depth
mm (in.)
kg (lb.)
kg (lb.)
3
m
(cu. ft)
, Outdoor air temperature 7 °C DB / 6 °C WB
I - 49
ECO MULTI SYSTEM Unit Specifications
SPW-AS123GH56
220 - 230 - 240 V / 1 phase / 50Hz
Cooling
3.6
12,000
580 / 520 / 450
1.5
220 - 230 - 240
198 – 264
0.34 - 0.35 -
0.36
70 -
75 -
80
93 -
93 -
93
1
-
1
Microprocessor / I.C. thermostat
ON / OFF Timer (Max. 72 hr)
3 and Automatic control
Washable, easy access
Electronic refrigerant control valve
38 / 35 / 31
Flare type
9.52 (3 / 8)
12.7 (1 / 2)
25 A, OD32 mm
Max. head 25 cm above drain connection
Optional (RCS-SH80TG)
Optional /
Unit dimensions
370 ( 14 - 5 / 8)
810 ( 31 - 7 / 8)
620 ( 24 - 3 / 8)
30 (
42 (
0.324 ( 11.6
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Heating
4.2
14,000
0.27 - 0.28 - 0.29
55 -
60 -
65
93 -
93 -
93
-
1
Package dimensions
485 ( 19 - 1 / 8)
918 ( 38 - 1 / 8)
728 ( 28 - 5 / 8)
66
)
93
)
)
SM830052
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents