( I ) Set the indoor unit address

This function is usable if the auto. address operation is not available.
Indoor unit address can be set one by one by remote controller in such case.
NOTE
1) In case of group control, branch wiring for group control should be removed temporarily.
2) In case of remote controllerless system, remote controller should be connected with the indoor unit
temporarily.
a
Short the two terminals of DISP PIN on indoor unit PCB.
(DISP PIN : Refer to P. VI–2)
b
Press the TEST / CHK , SET and CL buttons at the same time for more than 4 seconds.
AIR FLOW
UNIT
UNIT No.
R.C.
FLAP
TIMER SET
SET
CL
c
Set the CODE No. 12 to set the No. of R. C. with the
AIR FLOW
UNIT
UNIT No.
R.C.
FLAP
TIMER SET
SET
CL
MODE
No.
SET TEMP.
CODE
No.
FAN SPEED
SETTING
SET
DATA
ON
OFF
TEST / CHK
0367_M_I
MODE
No.
SET TEMP.
CODE
No.
FAN SPEED
SETTING
SET
DATA
ON
OFF
TEST / CHK
0368_M_I
III - 33
,
(SET TEMP) button.
Service Procedures
3
SM830052