Function Of Thermistor; Heat Pump Model - Daikin F-Series Service Manual

F-series inverter pair wall mounted type
Hide thumbs Also See for F-Series:
Table of Contents

Advertisement

Function of Thermistor

2. Function of Thermistor

2.1

Heat Pump Model

A
Outdoor Heat
1. The outdoor heat exchanger thermistor is used for controlling target discharge temperature.
Exchanger
Thermistor
2. The outdoor heat exchanger thermistor is used for detecting disconnection of the discharge
3. The outdoor heat exchanger thermistor is used for high pressure protection during cooling
B
Discharge
1. The discharge pipe thermistor is used for controlling temperature of the discharge pipe.
Pipe Thermistor
2. The discharge pipe thermistor is used for detecting disconnection of the discharge
C
Indoor Heat
1. The indoor heat exchanger thermistor is used for controlling target discharge temperature.
Exchanger
Thermistor
2. The indoor heat exchanger thermistor is used for preventing freezing.
3. During heating: the indoor heat exchanger thermistor is used for detecting disconnection of
42
A
Four way valve
B
The system sets a target discharge temperature according to the outdoor and indoor heat
exchanger temperature, and controls the electronic expansion valve opening so that the
target discharge temperature can be obtained.
thermistor when cooling.
When the discharge pipe temperature becomes lower than the outdoor heat exchanger
temperature, the discharge pipe thermistor is judged as disconnected.
operation.
If the temperature of discharge pipe (used in place of the inner temperature of the
compressor) rises abnormally, the operating frequency drops or the operation halts.
thermistor.
The system sets a target discharge pipe temperature according to the outdoor and indoor
heat exchanger temperature, and controls the electronic expansion valve opening so that
the target discharge temperature can be obtained.
During the cooling operation, if the temperature drops abnormally, the operating frequency
becomes lower, then the operation halts.
the discharge pipe thermistor.
When the discharge pipe temperature becomes lower than the indoor heat exchanger
temperature, the discharge pipe thermistor is judged as disconnected.
The indoor heat exchanger thermistor is also used for preventing abnormal high pressure.
Electrontic
expansion valve
Compressor
Si04-703A
C
(R5204)
Function and Control