Si04-703A
Step
3
Release the clamp by
pliers to detach the wire
harness for the
compressor.
4
Remove the putty.
Before working,
make sure that the
refrigerant is empty
in the circuit.
Be sure to apply
nitrogen
replacement when
heating up the
brazed part.
5
Heat up the brazed
parts indicated by the
arrows.
Removal Procedure
Procedure
Outdoor Unit
Points
The illustration is for 50/60
class heat pump models as
representative.
The illustration is for 50/60
class heat pump models as
representative.
Warning
Ventilate when refrigerant
leaks during the work.
(If refrigerant contacts fire, it
will cause to arise toxic gas.)
Provide a protective sheet or
a steel plate so that the
brazing flame cannot
influence peripheries.
Be careful so as not to burn
the compressor terminals or
the name plate.
Be careful so as not to burn
the heat exchanger fin.
Warning
Since it may happen that
refrigeration oil in the
compressor will catch fire,
prepare wet cloth so as to
extinguish fire immediately.