Outdoor Unit
Step
4
Remove the sound
blanket (top-lower).
Remove the sound
5
blanket (inner).
6
Release the
discharge
pipe
thermistor.
Cut the clamp by
7
nippers.
Disconnect the
outdoor
heat exchanger
thermistor.
174
Procedure
Si04-703A
Points
Since the piping ports on the
sound blanket (inner) are
torn easily, remove the
blanket carefully.
Pay attention to the direction
of the clip so as not to touch
the lead wire of the
thermistor when
reassembling.
Clamps should be always
available.
Fix it as it was before.