Daikin F-Series Service Manual page 123

F-series inverter pair wall mounted type
Hide thumbs Also See for F-Series:
Table of Contents

Advertisement

Troubleshooting
Troubleshooting
Check No.04
Refer to P.130
Check No.06
Refer to P.132
Check No.07
Refer to P.133
Check No.09
Refer to P.134
112
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check the installation space.
Check No. 07
Check the installation
condition.
Normal
Check No. 09
Check the outdoor fan.
Normal
Check No. 04
Check the electronic expansion valve.
Judgment
Normal
Check No. 06
Check the heat exchanger
thermistor.
Judgment
Normal
Abnormal
Abnormal
Abnormal
Abnormal
Si04-703A
Change the air outlet grille
position.
Change the installation
location.
Clean the heat exchanger.
Replace the fan motor.
Repair the connector or fan
motor lead wires.
Replace the electronic
expansion valve or coil.
Replace the PCB.
Replace the heat exchanger
thermistor.
Replace PCB.
(R7142)
Service Diagnosis