Venting Requirements; Venting Systems; Chimney Systems - Quadra-Fire 4100I-GD-B User Manual

4100-i act wood insert
Hide thumbs Also See for 4100I-GD-B:
Table of Contents

Advertisement

4100-I ACT Wood Insert

Venting Systems

Chimney Connector:
It is also known as flue pipe or stove pipe. It must be 6 inches
(152mm) minimum diameter stainless steel connector pipe.
Chimney:
The chimney can be new or existing, masonry or prefabricated
and must meet the following minimum requirements as
specified below.
WARNING! Risk of Fire!
Follow venting manufacturer's clearances and instructions
when installing venting system.
Inspections
Existing chimneys should be inspected and cleaned by a
qualified professional prior to installation. The chimney
must not have cracks, loose mortar or other signs of dete-
rioration and blockage. Hearth & Home recommends a
NFI or CSIA certified professional or a technician, under
the direction of a certified professional, conduct a Level II
inspection per NFPA 211.
Inspection of Chimney:
Chimney must be in good condition.
Meets minimum standard of NFPA 211
Factory-built chimney must be 6 inch
(152mm) UL10 HT.
Larger Chimneys
It is recommended that chimneys with larger diameters than
6 inches (152mm) be relined. An oversized flue can affect
draft and impair performance and will allow increased build-
up of creosote.
NOTICE: Check with your local building authorities
and/or consult the National Fire Protection Association
(NFPA 211).
Page 8

vENTING REqUIREMENTS

WARNING
Fire Risk

Chimney Systems

Approved Masonry Chimney:
• Must meet minimum standards of NFPA 211.
• Must have at least 5/8 inch (16mm) fireclay lining joined
with refractory cement.
without a stainless steel liner may reduce draw which
affects performance, will cause the glass to darken and
produce excessive creosote).
• The masonry wall of the chimney, if brick or modular
block, must be a minimum of 4 inches (102mm) nominal
thickness.
• A chimney of rubble stone must be at least 12 inches
(05mm) thick.
• Cross-sectional area should be no more than  times the
cross-sectional area of the flue collar of the insert. (28 sq
inch flue area x  inches = 84 square inches maximum
chimney area).
• Should be lined with a 6 inch (152mm) stainless steel
flue liner to improve performance and reduce creosote
build-up.
• A n equivalent liner must be a listed chimney liner system
or other approved material.
• No dilution air is allowed to enter the chimney.
1. Secure the fireplace damper in the open position. If
this cannot be accomplished, it will be necessary to
remove the damper
2. Seal damper area of chimney around chimney
connector with a high temperature sealant or seal
insert against the face of the fireplace.
. Both methods must be removable and replaceable
for cleaning and re-installation.
• When possible, install an airtight clean-out door to the
rear of the smoke shelf.
Minimum 1/2" (25mm) Air Space,
Maximum 4" (102mm) Air Space
Airtight Clean-
Out Door
Footing (depth and size of footing
accordance with local building code)
Figure 8.1
250-7201F
(Installations into a clay flue
Minimum 5/8" (16mm)
Fireclay Flue Liner
Non-Water Soluble
Refractory Mortar
4" (102mm) Masonry
or Modular Block Wall
(Nominal)
12" (305mm) if Rubble
Stone Wall (Nominal)
April 19, 2010
R

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

4100i-nl-b4100-i act

Table of Contents