Ovalizing Round Stainless Steel Liners; Chimney Height / Rise & Run; Air Clearances - Quadra-Fire 4100I-GD-B User Manual

4100-i act wood insert
Hide thumbs Also See for 4100I-GD-B:
Table of Contents

Advertisement

4100-I ACT Wood Insert

Ovalizing Round Stainless Steel Liners

Ovalizing round stainless steel liners to accommodate the
liner passing through the damper region of a fireplace is an
allowable and acceptable practice.
Ensure that the ovalization is minimized to the extent
required to fit through the damper.
Chimney Height / Rise and Run
To be sure that your Quadra-Fire insert burns properly, the
chimney draft (static pressure) should be approximately -0.10
inches water column (W.C.) during a high burn and -0.04
inches W.C. during a low burn, measured 6 inches (152mm)
above the top of the insert after one hour of operation at each
burn setting.
NOTE: These are guidelines only, and may vary somewhat
for individual installations.
• This product was designed for and tested on a 6 inch
(152mm) chimney, 14 to 16 feet (4.27-4.87m) high, (in-
cludes appliance height) measured from the base of the
appliance.
• The further your stack height or diameter varies from this
configuration, the possibility of performance problems ex-
ists.
• Chimney height may need to be increased by 2 - % per
each 1000 feet (04.8m) above sea level.
• It is not recommended to use offsets or elbows at altitudes
above 4000 feet (1219.2m) above sea level or when there
are other factors that affect flue draft.
Fire Risk.
Do NOT pack insulation or other combustibles
between spacers.
• ALWAYS maintain specified clearances around
venting and spacers.
• Install spacers as specified.
Failure to keep insulation or other material away from
vent pipe may cause fire.
WARNING! Risk of Asphyxiation!
Do NoT coNNecT This appliaNce To a chimNey
Flue serviciNg aNoTher appliaNce or To aNy
air DisTribuTioN DucT or sysTem.
This may allow flue gases to enter the house.
Page 12
WARNING

Air Clearances

To ensure that insulation or any other combustible material
does not contact the chimney follow clearances below:
• A chimney inside the house must have at least 2 inches
(51mm) of clearance to the combustible structure.
• A chimney outside the house must have at least 1 inch
(25mm) clearance to the combustible structure.
• Non-combustible fire stops must be installed at the spaces
where the chimney passes through floors and/or ceilings.
Figures 12.1 and 12.2.
Minimum 2 inch (51mm) clearance
from combustible material
and insulation
Figure 12.1
Non-Combustible
Firestopping
Material
Floor
(second Story)
Figure 12.2
250-7201F
ceiling
Non-combustible
fire stopping material
Firestopping
2 inch
(51mm)
Ceiling
Caulk
Minimum 1 inch (25mm)
clearance from exterior
chimney to sheathing
April 19, 2010
R
Floor