Bosch RC35 Installation And Service Instructions Manual page 34

Logamatic ems programming unit room controller
Table of Contents

Advertisement

System settings (Service menu – Settings)
6
Menu item
What is the desired
maximum flow
temperature?
For how many days
should maximum flow
temp. be maintained?
Every how many days
should the flow temp.
be reduced?
By how many K should
the flow temperature
be reduced
respectively?
Do you wish to change
the switching program?
Should the switching
programme be
optimised?
What reduction mode
should be used for
holiday?
What outside temp.
should be used?
Table 14 Navigator for service menu of SETTING\HEATING CIRCUIT 1
1) Depending on the boiler the setting range can be limited
2) Not possible or not available with boilers with UBA1.x or DBA.
34
Input range
25 °C to 60 °C
0 days to 20 days
Direct normal
operat., every day,
every 2nd day to
every 5th day
0 K to 20 K
Yes, No
Yes, No
Outdoor
compensation
mode,
reduced mode,
room compensation
mode, switch-off
mode
-20 °C to +10 °C
Standard
setting
Other information
2)
45 °C
2)
4 days
2)
Every day
5 K
Adjustment only if, for flow
temperature reduction,"direct
normal operation" has not been
selected.
no
When selecting "yes" the system
jumps to the heating circuit
switching program.
no
Start and stop times are
automatically adjusted according to
the outside temperature, room
temperature and building type (heat
storage capacity).
Outdoor
See page 37.
setback
Setting for "room compensation
mode
mode" only if a remote programmer
(e.g. RC2x) has been allocated to
the heating mode. If "reduced
mode" is selected, the normal night
temperature is used.
5 °C
Temperature threshold for outdoor
setback mode (
Adjustment only if setback mode for
holiday was set to "outdoor setback
mode."
4)
page 37).
Logamatic EMS – 6 720 801 387 (2011/05)