Start Output Device Mapping by pressing *79 while in Data Programming Mode. The
following prompts are displayed:
∗ ∗ ∗ ∗ 79 Menu Mode
PROMPT
ENTER OUTPUT NO.
00 = QUIT
xx
17 OUT NORM LOW
0 = NO 1 = YES
0
XX OUTPUT TYPE
DELETE
0
"A"
XX UNIT No.
yy
"B"
XX MODULE ADDR
yy
5-14
VALID ENTRIES
Device Output Number
01-04,
17-18 = relays/X-10
[∗] to continue
Output Normally Low
0 = no (standard default)
1 = yes
[∗] to continue
Output Type
0 = delete
1 = relay on 4204/4229 module
or 6164 keypad
2 = Powerline Carrier device
[∗] to continue

Unit Number

01-04 = predefined address
[∗] to continue
Module Address
08 = predefined address
[∗] to continue
EXPLANATION
This is the logical (or reference) relay number as
used in the system. Relays and X-10 devices are
numbered 01-04; the on-board triggers are
numbered 17 and 18 and can be programmed for
inverted output. Use the worksheet on the
Programming Form (printed separately) to
organize device numbers.
This prompt appears only for triggers 17 and 18.
Selecting 0 (no) sets the output level normally
high.
Selecting 1 (yes) sets the output normally low.
Output trigger 17 can be used for resetting 4-wire
smoke detectors by connecting it to the negative
power terminal of the smoke detector, selecting 1
at this prompt, and setting as zone type 54, fire
zone reset, in *80 Menu mode.
After entry, display returns to Output Number
prompt. Use *80 Menu mode to program the
function of the trigger.
Select whether this is a relay or a Powerline
Carrier (X-10) device.
If relay is selected, skip to "B" prompt.
If X-10 is selected, go to "A" prompt.
If X-10 is selected, a prompt for the unit number
appears.
Enter the unit code (set at the device) and press
[∗].
The system returns to the Output Number
prompt.
If relay is selected, this prompt appears.
Enter the predefined address for this module as
listed below. Make sure the module's DIP
switches are set to the selected address (6164
keypad address is entered via its keypad
programming prompts).
Module Address
Address
Module or Keypad
08
4229 (with zones 17-24)