Smoke Detectors - Honeywell ADEMCO Vista-12C Installation And Setup Manual

Table of Contents

Advertisement

Installation and Setup Guide

Smoke Detectors

2-Wire Smoke Detectors
1. Connect up to sixteen 2-wire smoke detectors across
zone 1 terminals 8 (+) and 9 (-) as shown in the
Summary of Connections diagram. Observe proper
polarity when connecting the detectors.
2. Connect an EOL resistor across the loop wires at the
last detector.
4-Wire Smoke Detectors
3. Connect 4-wire smoke detectors (up to 16, depending
on detector current drain) to any zone from 2-6 as
shown below. This control does not automatically reset
power to 4-wire smoke detector zones, so you must use
a relay (e.g., 4204, 4229), or on-board trigger 17 to
reset power (also required for fire verification). Do this
by programming the designated relay/trigger as zone
type 54 (fire zone reset); see On-Board Trigger section
for other information.
+
5
RELAY
PROGRAM
AUX PWR
RELAY
OUTPUT
AS ZONE
TYPE 54
TERMINALS
(FIRE ZONE
RESET)
_
4
N.C.
CONTACT OPENS
MOMENTARILY UPON
FIRE ALARM RESET
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
TO ZONE TERM. ( )
+
HEAT
DETECTOR
_
TO ZONE TERM. ( )
4-Wire Smoke Detector Using Relay for Power Reset
2-8
Figure 6. 4-Wire Smoke Detector Connections
_
BLK
+
RED
EOL
POWER
N.O.
SUPERVISION
RELAY MODULE
A77-716B.
USE N.O.
CONTACT,
+
_
WHICH CLOSES
VIOLET
WHEN POWER
IS APPLIED.
2000
OHMS
EOLR
PROGRAM OUTPUT 17
FOR "OUT NORM
LOW" = YES IN
MODE AND AS ZONE
80 MENU MODE
Notes
• • • • Fire Verification (zone type 16):
The control panel will "verify" a fire
alarm by resetting the smoke
detectors after the first alarm trigger,
and then waiting 90 seconds for a
second alarm trigger. If the smoke
detector does not trigger again, the
control will disregard the first trigger,
and no alarm signal will occur. This
feature eliminates false alarms from
smoke detectors due to electrical or
physical transients.
• The zone 1 alarm current supports
only one smoke detector in the
alarmed state.
• Do not use 4-wire smoke detectors on
zone 1.
• Maximum current for trigger 17
output for 4-wire smoke detectors is
100mA.
+
( )
5
AUX PWR
_
TO OUTPUT 17
( )
79 MENU
+
TYPE 54 IN
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
TO ZONE TERM. ( )
+
HEAT
DETECTOR
_
TO ZONE TERM. ( )
4-Wire Smoke Detector Using Output 17 for Power Reset
_
BLK
+
RED
EOL
POWER
SUPERVISION
N.O.
_
RELAY MODULE
VIOLET
A77-716B.
USE N.O.
2000
CONTACT,
WHICH CLOSES
OHMS
WHEN POWER
EOLR
IS APPLIED.