DSC PowerSeries PC1616 Installation Manual page 16

V4.6 na security system
Hide thumbs Also See for PowerSeries PC1616:
Table of Contents

Advertisement

[11]
System Tamper: Output will activate when any tamper condition is present
[12]
TLM and Alarm: Output will activate if a telephone line trouble is present and then an alarm occurs
[13]
Kissoff: Output will activate for 2 seconds when a valid kissoff is received from the central station
Ground Start: Output will activate for 2 seconds when the panel attempts to seize the phone line (additional dial tone search must
[14]
be programmed in the central station phone number – HEX [D])
Remote Operation: Output can be activated/deactivated via the DLS software
[15]
[16]
For Future Use
[17]
Away Armed Status: Activates when all of the selected partitions are armed in Away mode
Stay Armed Status: Activates when all of the selected partitions are armed in Stay mode
[18]
[19]
Command Output 1: Activates when a [,][7][1] command is entered on the selected partition – Command can be programmed to require
a valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
[20]
Command Output 2: Activates when a [,][7][2] command is entered on the selected partition – Command can be programmed to require
a valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
[21]
Command Output 3: Activates when a [,][7][3] command is entered on the selected partition – Command can be programmed to require
a valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
[22]
Command Output 4: Activates when a [,][7][4] command is entered on the selected partition – Command can be programmed to require
a valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
[23]
Silent 24-Hour Input: Changes PGM to a 24-hr Silent zone (PGM2 only)
[24]
Audible 24-Hour Input: Changes PGM to a 24-hr Audible zone (PGM2 only)
Delayed Fire and Burglary: Functions as a Fire and Burglary output but does not activate until the TX Delay time expires
[25]
[26]
Battery Test Output: Output activates for 10 seconds at midnight each day.
[27]
For Future Use
Holdup Output: Activates when a Holdup Alarm occurs on any assigned partition. Remains active until all assigned partitions have
[28]
been armed or disarmed. Will not activate if a Holdup Zone goes into a fault or tamper condition.
Zone Follower (Zones 1-8): Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
[29]
[30]
Partition Status Alarm Memory: Activates if the selected partition is armed. Output will pulse "one second ON / one second OFF
if an alarm occurs
[31]
Alternate Communicator: Activates when selected system event occurs. If active in the armed state, it remains active until the sys-
tem is disarmed. If activated in the disarmed state, it remains active until a valid access code is entered within the bell cut-off time, or
when the system is armed after the bell cut-off time has expired.
For Future Use
[32]
[33]
For Future Use
[34]
Away Armed with no Zone Bypassed Status: Activates when armed with stay/away zones active and no zones bypassed.
Zone Follower (Zones 9-16):
[35]
[36]
Zone Follower (Zones 17-24):
[37]
Zone Follower (Zones 25-32):
Zone Follower (Zones 33-40):
[38]
[39]
Zone Follower (Zones 41-48):
[40]
Zone Follower (Zones 49-56):
Zone Follower (Zones 57-64):
[41]
* See Section [501]-[514] Programmable Output Attributes, PGM Output Option [29] and [35]-[41] Option 8 on 24.
[012] Keypad Lockout
The system can be programmed to 'lockout' keypads if a series of incorrect user or installer codes are entered. When lockout is active, all
keypads emit a steady 2-second error tone when a key is pressed. Program the Number of Invalid Codes Before Lockout with the desired
number. Valid entries are from [000] to [255]. Program data [000] to disable the feature. Keypads will remain locked out for the number of
minutes programmed for the Lockout Duration. Valid entries are from [000] to [255].
Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
13
Chapter 4 Programming Descriptions