Siemens MICROMASTER 430 Operating Instructions Manual page 84

7.5kw-90kw 3ac-frequency inverters for controlling the speed of three phase ac motors
Hide thumbs Also See for MICROMASTER 430:
Table of Contents

Advertisement

6 Troubleshooting
Fault
Possible Causes
Motor data identification failed.
F0041
Alarm value =0: Load missing
Motor Data
Alarm value =1: Current limit level
Identification
reached during identification.
Failure
Alarm value =2: Identified stator
resistance less than 0.1% or
greater than 100%.
Alarm value =3: Identified
rotorresistance less than 0.1% or
greater than 100%.
Alarm value =4: Identified stator
reactance less than 50% and
greater than 500%
Alarm value =5: Identified main
reactance less than 50% and
greater than 500%
Alarm value =6: Identified rotor time
constant less than 10ms or
greater than 5s
Alarm value =7: Identified total
leakage reactance less than 5%
and greater than 50%
Alarm value =8: Identified stator
leakage reactance less than 25%
and greater than 250%
Alarm value =9: Identified rotor
leakage inductance less than
25% and greater than 250%
Alarm value = 20: Identified IGBT on-
voltage less than 0.5 or greater
than 10V
Alarm value = 30: Current controller
at voltage limit
Alarm value = 40: Inconsistence of
identified data set, at least one
identification failed
Percentage values based on the
impedance Zb = Vmot,nom / sqrt(3) /
Imot,nom
Read or write failure while saving
F0051
non-volatile parameter.
Parameter
EEPROM Fault
Read failure for power stack
F0052
information or invalid data.
Power stack
Fault
Read failure for IO EEPROM
F0053
information or invalid data.
IO EEPROM
Fault
Wrong IO board is connected.
F0054
No ID detected on IO board, No
Wrong IO
data.
Board
Internal communications failure
F0060
Asic Timeout
No setpoint values from CB
F0070
(communication board) during
CB setpoint
telegram off time
fault
No setpoint values from USS during
F0071
telegram off time
USS (BOP-
link) setpoint
fault
84
Diagnose & Remedy
0:
Check that the motor is connected to the
inverter.
1-40: Check if motor data in P304-311 are correct.
Check what type of motor wiring is required (star,
delta).
1.
Factory Reset and new parameterization
2.
Change drive
Change drive
1.
Check data
2.
Change IO module
1.
Check data
2.
Change IO module
1.
If fault persists, change inverter,
2.
Contact Service Department
Check CB and communication partner
Check USS master
MICROMASTER 430
Issue 05/02
Reac-
tion
OFF1
OFF1
OFF1
OFF2
OFF2
OFF1
OFF1
OFF1
Operating Instructions
6SE6400-5AE00-0BP0