A.5.2
TFTP Method - Web Interface
To update the Liebert IntelliSlot card firmware using the TFTP method with a Web interface:
Open a Connection to the Card
1. Open a connection to the Liebert IntelliSlot card (if needed, see instructions in A.2.4 - Open the
Web Interface).
2. Click on the Configure tab, then TFTP in the left panel.
Configure
tab
3. Enter the Administrator username and password (both are case-sensitive):
a. Login (username—default is Liebert)
b. Password (default is Liebert)
Specify TFTP Server and Upgrade Filename
4. Click the Edit button in the right panel.
5. Select options as needed and refer to the following guide to change any settings.
Table A5
Firmware update settings - Web
Parameter
Server
The IP address of the TFTP server—for example, 192.168.0.125.
Port
Port that the TFTP server is using, typically 69.
Name of the firmware update file—128 characters maximum, including spaces and punctuation.
Filename
This is the file with the extension ".bin" downloaded in A.3.3 - Download the Firmware Upgrade
File to the Computer.
6. After making changes, click Save, then click Reinitialize in the left panel to reboot the card.
Configure
tab
Reinitialize
Reconnect to the Card
7. Click the Configure tab, then TFTP and enter the username and password (Steps 2 and 3) to
return to the TFTP screen as shown above.
Updating the Firmware - TFTP (HyperTerminal, Telnet, Web) Method