10.4

BACnet/IP Server Menu

Once BACnet/IP is activated (as described in Section 10.2),
the Management Protocol menu displays BACnet/IP as enabled
and provides access to the BACnet/IP Configuration menu.
The BACnet/IP Server menu allows you to specify BACnet/IP
protocol settings for the Web card.
Terminal Emulation (Serial or TCP/IP Connection) / Telnet
To access the BACnet/IP Server Menu:
1. Choose IP Network Settings from the Main Menu.
2. Choose Management Protocol from the IP Network
Settings Menu.
3. Choose BACnet/IP Server.
4. Choose an option from the BACnet/IP Server menu:
Table 27
BACnet/IP Server Menu options
Feature
BACnet Write
Access
Device Instance
Number
Device Object
Name
APDU Timeout
APDU Retries
Supported Data
List
Web Interface
To configure BACnet/IP through the Web interface:
• Click on the Configure tab, then BACnet in the left panel under Management Protocol and
finally Edit at right. After making changes, click Save.
Configure tab
BACnet
Building Management Functions (IS-IPBML & IS-IPBMS Cards Only)
Allows the BACnet server to write to the managed device.
Note: Checking this feature enables or disables write operations by the BACnet interface only.
Write operations may still be available from other system interfaces.
Assign an instance number for this device object (0-4194303).
Note: A restart of the system is required before a change to this value will take effect.
ASCII string as name of this device (32 characters maximum).
Note: Setting this value to "-" will reset it to the factory default name.
Timeout in milliseconds for APDU (1-65535 ms).
Retry times for APDU (0-8).
For detailed instructions, see 10.4.1 - Supported Data List - BACnet/IP.
Management Protocol Menu
-------------------------
1: Select Managed Protocol
2: BACnet/IP Server
<ESC>: Cancel menu level
Please select a key ?>
BACnet/IP Server Menu
----------------------
1: BACnet Write Access
2: Device Instance Number 1130000
3: Device Object Name
4: APDU timeout
5: APDU Retries
6: Supported Data List
<ESC>: Cancel menu level
Please select a key ?>
Description
59
BACnet/IP
Enabled
Device1130000
3000
3