Summary of Contents for Liebert IntelliSlot

  • Page 1 Liebert IntelliSlot Web Card, Liebert IntelliSlot Web Card-LB, Liebert IntelliSlot Web Card-LBDS, Liebert IntelliSlot Web Card NXL ™ , Liebert IntelliSlot Web Card-L, Liebert IntelliSlot Web Card-IPBML Modbus IP / BACnet IP, Liebert IntelliSlot Web Card-S, Liebert IntelliSlot Web Card-IPBMS Modbus IP, Liebert IntelliSlot Web/485 Card With Adapter...
  • Page 3: Table Of Contents

    Prepare the Card for Configuration ..........5 Install a Liebert IntelliSlot Web/485 Card With Adapter ......6 3.2.1...
  • Page 4 ..........13 QUIPMENT NFORMATION .
  • Page 5 Monitoring Liebert Equipment ........
  • Page 6 Liebert IntelliSlot card communication protocols ........
  • Page 7: Important Safety Instructions

    SAVE THESE INSTRUCTIONS WARNING Only a qualified service professional should install these products. Emerson recommends having an Emerson Network Power Liebert Services representative perform the installation in large UPSs. Contact Liebert Services at 1-800-LIEBERT (1-800-543-2378). WARNING Risk of electric shock. Can cause equipment damage, injury or death.
  • Page 8: Introduction

    The Liebert IntelliSlot Web Card family delivers enhanced communications and control to Liebert UPS, AC Power and Precision Cooling systems. Liebert IntelliSlot Web cards bring SNMP, Telnet, Modbus IP and BACnet IP and Web-management capability to many models of Emerson Network Power’s line of Liebert UPS, power and cooling equipment.
  • Page 9: Compatibility With Other Emerson Products And Communication Protocols

    SNMP v3 available for Liebert GXT3 only ** Modbus IP only for IS-IPBMS *** Liebert DataMate & Mini-Mate support BACnet IP only on IS-WEBADPT (Modbus IP is not available on these units). Liebert IntelliSlot Web cards support both 10Mbit and 100Mbit communication speeds and either half or full duplex.
  • Page 10: Web Support

    Liebert Nform ™ Support Utilizing the SNMP and Web technologies built into each of the Liebert IntelliSlot Web cards, Liebert Nform will centrally manage alarm notifications to provide you with an easy interface to access criti- cal equipment information. A downloadable edition is available online at: nform.liebert.com...
  • Page 11: Installation

    Follow these steps to install a Liebert IntelliSlot Web card (non-adapter version—P/N IS-WEBCARD, IS-WEBLB, IS-WEBLBDS, IS-WEBNXL, IS-WEBL, IS-IPBML, IS-WEBS and IS-IPBMS). 1. Locate the Liebert IntelliSlot option bay on your Liebert equipment—You might need to remove a plastic cover. 2. Insert the Liebert IntelliSlot Web Card into the Liebert IntelliSlot bay.
  • Page 12: Install A Liebert Intellislot Web/485 Card With Adapter

    10. Choose Exit and Save to save your changes and reboot the card. NOTE When installing the card in a Liebert NX, configure the communication port of the Liebert NX to 2400 baud. See the Liebert NX user manual for details.
  • Page 13: Configuration Overview

    Configuration Overview ONFIGURATION VERVIEW You may use any of the following interfaces to configure the Web card: Table 5 Configuration interfaces Available Connection Interface Icon Description Functions Methods Terminal Emulation Use terminal emulation software Serial Cable Configuration (Serial or TCP/IP) —for example, HyperTerminal.
  • Page 14: Open The Terminal Emulation Interface - Serial Connection

    Configuration Overview Open the Terminal Emulation Interface - Serial Connection To access configuration using terminal emulation software with a serial connection to the Web card: 1. Open a terminal emulation application, such as Name HyperTerminal. To do this: • Click the Start button, then Programs, Accessories, Communications and finally HyperTerminal.
  • Page 15: Open The Terminal Emulation Interface - Tcp/Ip Connection

    Enter key. Service Port Manager Active 5. Enter the Administrator username and password (both are case- <Esc> Ends Session sensitive): a. Login (username—default is Liebert) Login: Liebert b. Password (default is Liebert) Password: ******** NOTE For security, change the default username and password (see 5.7 - Change Username / Password - Administrator and General User).
  • Page 16: Open The Telnet Interface

    Configuration Overview Open the Telnet Interface To access configuration using Telnet: 1. Open a Telnet connection on a computer with an Ethernet connection to the Liebert unit. To do this: • Open a command prompt window—click the Start button, then Run.
  • Page 17: Open The Web Interface

    3. Click on any configuration category, and the Connect To box opens. 4. Enter the Administrator username and password (both case-sensitive): a. User Name (default is Liebert) b. Password (default is Liebert) NOTE For security, change the default username and password (see 5.7 - Change Username /...
  • Page 18: Saving Changes And Reinitializing The Web Card

    Configuration Overview Saving Changes and Reinitializing the Web Card Follow the applicable steps for your interface to save configuration changes and reinitialize the Web card. Changes will not take effect until these steps are completed. Terminal Emulation (Serial or TCP/IP Connection) / Telnet New Settings will take effect when saved •...
  • Page 19: Equipment Information

    Equipment Information QUIPMENT NFORMATION Equipment Information is optional and identifies the Liebert unit, its Equipment Information Menu location, a contact person and other information about the unit. The --------------------------- 1: Name Uninitialized default value of each field is “Uninitialized.” 2: Contact...
  • Page 20: Network Settings

    Network Settings ETWORK ETTINGS The IP Network Settings Menu is used to enable network IP Network Settings Menu communications with the Web card. ------------------------- 1: Boot/IP Settings Refer to the following sections for detailed step-by-step 2: Domain Name Server (DNS) Settings 3: Management Protocol instructions on each item from this menu: 4: Web Server...
  • Page 21: Boot/Ip Settings

    Boot Mode • DHCP - Central management using dynamic network addresses • BootP - Older mechanism for central management of network addresses Network address for the Liebert unit. IP address Four numbers (0-255) separated by periods (.)—for example, 10.0.0.5 Network mask that divides your network into manageable segments.
  • Page 22: Domain Name Server (Dns) Settings

    Network Settings Domain Name Server (DNS) Settings The Domain Name Server settings menu configures the servers the Web card will use for hostname resolution. When configured, host addresses for SNMP, Network Time and Email/SMS can be speci- fied in either full Domain Name format or in host-only format, provided that the appropriate Domain Name Suffix is used.
  • Page 23 Network Settings Web Interface To access the DNS menu through the Web interface: • Click on the Configure tab, then DNS in the left panel under Network Settings and finally Edit beneath the table of parameters and descriptions. After making changes, click Save. Configure tab Click Edit to change...
  • Page 24: Management Protocol

    1: Authentication Traps access privileges and configure the Web 2: RFC-1628 (UPS) MIB enabled card to send traps for SNMPv1/v2c and - Traps enabled 4: Liebert Global Products MIB enabled SNMPv3. - Condition Traps enabled SNMP - System Notify Trap enabled Refer to 5.3.1 - SNMP Communications...
  • Page 25: Snmp Communications Menu

    See 5.3.4 - Display/Modify SNMPv3 Settings (Units with IS-WEBCARD Only). View a list of all supported events and parameters for the Liebert equipment through any interface. Depending on the Liebert IntelliSlot Web card, the list might Support Information include SNMP, Modbus or BACnet.
  • Page 26 Network Settings Web Interface To access SNMP Communications settings (for Authentication Traps, RFC-1628 (UPS) MIB, Liebert Global Products MIB and Heartbeat Trap Interval options) through the Web interface: • Click on the Configure tab, then SNMP in the left panel (under Management Protocol) and finally Edit in the right panel.
  • Page 27: Display/Modify Snmpv1/V2C Communities

    Network Settings 5.3.2 Display/Modify SNMPv1/v2c Communities View or modify devices that have permission to access the Web card, identified by IP address or host- name, read/write permission and community string. Choose IP Network Settings from the Main Menu, then Management Protocol. Up to 20 devices may be configured for access.
  • Page 28 Network Settings Web Interface To access SNMPv1/v2c Communities settings through the Web interface: • Click on the Configure tab, then Access or V1 Access (under Management Protocol) in the left panel and finally Edit in the right panel. After making changes, click Save. Configure Click on Edit V1 Access...
  • Page 29: Display/Modify Snmpv1/V2C Trap Communities

    Network Settings 5.3.3 Display/Modify SNMPv1/v2c Trap Communities View or modify devices that are configured to receive notifications from the Web card, identified by IP address or hostname, trap listen port and community string. Up to 20 devices may be configured to receive traps. EXAMPLE Trap Communities -----------------...
  • Page 30 Network Settings Web Interface To access SNMPv1/v2c Trap Communities settings through the Web interface: • Click on the Configure tab, then Traps or V1 Traps (under Management Protocol) in the left panel and finally Edit in the right panel. After making changes, click Save. Configure Click on Edit...
  • Page 31: Display/Modify Snmpv3 Settings (Units With Is-Webcard Only)

    Network Settings 5.3.4 Display/Modify SNMPv3 Settings (Units with IS-WEBCARD Display/Modify SNMPv3 Settings Menu Only) ------------------------------------ Engine ID: 00000063000000a17e04145c View or modify SNMPv3 devices that have permission to access 1: Display/Modify SNMPv3 Users the Web card, identified by IP address and other parameters. <ESC>: Cancel menu level Please select a key ?>...
  • Page 32 Network Settings Web Interface (Units with IS-WEBCARD Only) To access SNMPv3 settings through the Web interface: • Click on the Configure tab, then V3 Settings (under Management Protocol) in the left panel and finally Edit in the right panel. After making changes, click Save. Configure V3 Settings Configure up to 20 devices...
  • Page 33: Web Server

    Network Settings Web Server Web Server Menu ---------------- Use the Web Server Menu to configure access to the card 1: Web Server Mode HTTP (Not Secure) 2: HTTP Transport Port through the Web interface. Consult your network adminis- 3: Password Protect Site 'disabled' trator if needed.
  • Page 34: Install Security Certificates - Internet Explorer 6 Or Earlier

    Network Settings 5.4.2 Install Security Certificates - Internet Explorer 6 or earlier If you use Internet Explorer 6 or an earlier version and select HTTPS as the operation mode of the Web server (see 5.4.1 - Specify Web Server Settings), follow these instructions to install a security certificate.
  • Page 35 Network Settings • In the Certificate window, click the Install Certificate button, as shown below. Install Certificate • The Certificate Import Wizard opens. Click Next. Automatically select... • Click on Automatically select the certificate store based on the type of certificate, then click Next.
  • Page 36: Install Security Certificates - Internet Explorer 7 Or Later

    Network Settings 5.4.3 Install Security Certificates - Internet Explorer 7 or later If you use Internet Explorer 7 or later and select HTTPS as the operation mode of the Web server (see 5.4.1 - Specify Web Server Settings), follow these instructions to install a security certificate. To do this: •...
  • Page 37 Network Settings • In the Certificate window, click the Install Certificate button, as shown below. Install Certificate • The Certificate Import Wizard opens. Click Next. Automatically select... • Click on Automatically select the certificate store based on the type of certificate, then click Next.
  • Page 38: Telnet Server

    Network Settings Telnet Server Telnet Server Menu ------------------- Use the Telnet Server Menu to enable or disable access to the Web 1: Telnet Server 'enabled' card through a Telnet interface. <ESC>: Cancel menu level Please select a key ?> Terminal Emulation (Serial or TCP/IP Connection) / Telnet To change this setting: 1.
  • Page 39: Time (Sntp) Menu

    Network Settings Time (SNTP) Menu Time Server Menu ------------------- This permits setting time options—how often the Web card 1: SNTP Time Sync Rate Hourly 2: Time Server time.nist.gov synchronizes with the Time Server, which Time Server to use 3: Time Zone (GMT) UTC for synchronization and which the Time Zone the Web card is <ESC>: Cancel menu level...
  • Page 40: Change Username / Password - Administrator And General User

    • Change General Username/Password 2. Enter a user name—the current user name is shown in brackets. Enter Administrator Username, press enter for [Liebert]: (Max 32 chars) ?> 3. Enter a password, then verify by typing the password again. Enter New Password: (Max 32 chars) ?> ******** Verify Password: ?>...
  • Page 41: Reset Web Authentication To Factory Defaults

    To enter a new username and password, see 5.7 - Change Username / Password - Administrator and General User. Table 18 Factory default passwords Type of User Factory Default Description Username Liebert Full access to configuration and control Administrator functions, as well as viewing privileges Password Liebert Username User Viewing privileges only—no access to...
  • Page 42: Messaging

    Messaging ESSAGING The Messaging menu is used to set up e-mail and text message notifications Messaging Menu from the Web card. --------------- 1: Email 'disabled' 2: SMS 'disabled' Terminal Emulation (Serial or TCP/IP Connection) / Telnet 3: Email Configuration 4: SMS Configuration To access these options: <ESC>: Cancel menu level 1.
  • Page 43: E-Mail Configuration

    Messaging E-Mail Configuration Email Configuration Menu ------------------------- Setting up event notifications to be sent via e-mail involves two steps: 1: Email From 'Uninitialized' 2: Email Message Recipients enabling the function, then specifying the parameters. 3: Email Subject 4: Email Customize Message 5: SMTP Server 'Uninitialized' Terminal Emulation (Serial or TCP/IP Connection) / Telnet...
  • Page 44: Sms Configuration

    Messaging SMS Configuration SMS Configuration Menu ----------------------- Setting up event notifications for SMS text messages involves two 1: SMS From 'Uninitialized' 2: SMS Message Recipients steps: enabling the function, then specifying the parameters. 3: SMS Subject 4: SMS Customize Message 5: SMTP Server 'Uninitialized' Terminal Emulation (Serial or TCP/IP Connection) / Telnet...
  • Page 45: Customize Messages

    Description of the SNMP event 9.0 - Support Information Event Date & Time The date & time when the SNMP event occurred — Name The name for the Liebert unit Contact The contact person or department 4.0 - Equipment Information...
  • Page 46: Factory Settings

    The Factory Settings menu allows you to restore factory default settings and offers other options that may vary by the Liebert unit where the card is installed. Refer to the following sections for details: • 7.1 - Reset to Factory Defaults •...
  • Page 47: Advanced Communication Settings

    4. Choose Node ID from the Local Node Settings Menu, then use the following guide and Table 23 to make changes. If the Liebert unit has two Liebert IntelliSlot cards of the same type—Web or 485—change the address of one card: •...
  • Page 48: Managed Device Settings (Units With Is-Webnxl, Is-Webl, Is-Ipbml, Is-Webs, Is-Ipbms Cards Only)

    Factory Settings Menu IS-WEBS, IS-IPBMS Cards Only) ---------------------- 1: Advanced Communication Settings Use this menu to change router settings for Liebert units with 2: Agent Event Log IS-WEBNXL, IS-WEBL, IS-IPBML, IS-WEBS or IS-IPBMS cards 3: Reset to Factory Defaults 4: Support Information (see Table 1).
  • Page 49: Agent Event Log

    IS-IPBML, IS-WEBS, IS-IPBMS Cards Only) ---------------------- 1: Advanced Communication Settings Use this menu to enable or disable the event log for Liebert units 2: Agent Event Log 3: Reset to Factory Defaults with IS-WEBNXL, IS-WEBL, IS-IPBML, IS-WEBS or IS-IPBMS 4: Support Information cards (see Table 1).
  • Page 50: Realtime Information

    IS-IPBML, IS-WEBS, IS-IPBMS Cards Only) ---------------------- 1: Advanced Communication Settings Use this menu to display task stack usage for Liebert units with 2: Agent Event Log 3: Reset to Factory Defaults IS-WEBNXL, IS-WEBL, IS-IPBML, IS-WEBS or IS-IPBMS cards 4: Support Information...
  • Page 51: Monitor And Control Functions - Web Only

    • Equipment Information - name, contact, location and description of the Liebert unit (as defined in 4.0 - Equipment Information) • Device Status - current status of the Liebert unit and whether any alarms are active (if so, the most recent alarm is listed) •...
  • Page 52: Controlling Liebert Equipment

    Control functions. Clicking on a category changes the view in the right panel. The example above shows the summary page. The following guide is a partial list of Control operations—these vary by the type of Liebert unit. Table 24 Control operations parameters—functions vary by Liebert unit...
  • Page 53: Event Log

    Event Log NOTE For Liebert units with IS-WEBL, IS-IPBML, IS-WEBS or IS-IPBMS cards (see Table 1), the Web interface has a Data/Logs tab instead of the Event Log tab. For details, refer to 8.4 - Data/Logs Tab (Units with IS-WEBL, IS-IPBML, IS-WEBS, IS-IPBMS Cards Only).
  • Page 54: Data/Logs Tab (Units With Is-Webl, Is-Ipbml, Is-Webs, Is-Ipbms Cards Only)

    Monitor and Control Functions - Web Only Data/Logs Tab (Units with IS-WEBL, IS-IPBML, IS-WEBS, IS-IPBMS Cards Only) The Data/Logs tab offers the following features for Liebert units with IS-WEBL cards (see Table 1). Table 25 Data/Logs tab features (Units with IS-WEBL Cards Only)
  • Page 55: Downloads (Units With Is-Webl, Is-Ipbml, Is-Webs, Is-Ipbms Cards Only)

    8.4.1 Downloads (Units with IS-WEBL, IS-IPBML, IS-WEBS, IS-IPBMS Cards Only) You may download event logs, data logs and other files stored in the Liebert unit. To download or view a file: • Click on the Data/Logs tab at the top of the window.
  • Page 56: Event Log Agent (Units With Is-Webl, Is-Ipbml, Is-Webs, Is-Ipbms Cards Only)

    Monitor and Control Functions - Web Only 8.4.2 Event Log Agent (Units with IS-WEBL, IS-IPBML, IS-WEBS, IS-IPBMS Cards Only) The Event Log Agent allows viewing events stored in the Web card’s history. This history is gathered only when the Web card is installed and communicating properly with the device. The history is stored in descending chronological order;...
  • Page 57 Monitor and Control Functions - Web Only 8.4.3 Events and Parameters (Units with IS-WEBL, IS-IPBML, IS-WEBS, IS-IPBMS Cards Only) You may view a list of all supported SNMP events and parameters for the Liebert equipment through the Web interface. To view this data: •...
  • Page 58: Support Information

    NFORMATION Support data includes identifying information for the Web card, as well as events and parameters available for the Liebert equipment. View Web Card Information Identifying information for the Web card may be viewed through any interface and includes the MAC address, model and part number, serial number and firmware version.
  • Page 59: Events And Parameters

    Support Information Events and Parameters You may view a list of all supported events and parameters for the Liebert equipment through any interface. Depending on the Liebert IntelliSlot Web card, the list might include SNMP and Modbus. Terminal Emulation (Serial or TCP/IP Connection) / Telnet...
  • Page 60: Building Management Functions (Is-Ipbml & Is-Ipbms Cards Only )

    This information in this section provides details on Modbus IP and BACnet IP functions that apply only to these cards: • Liebert IntelliSlot Web Card-IPBML Modbus IP or BACnet IP (IS-IPBML) • Liebert IntelliSlot Web Card-IPBMS Modbus IP (IS-IPBMS) For other functions, see the appropriate section in this manual.
  • Page 61: Management Protocol Menu - Choose Modbus/Tcp Or Bacnet/Ip

    Building Management Functions (IS-IPBML & IS-IPBMS Cards Only) 10.2 Management Protocol Menu - Choose Modbus/TCP or BACnet/IP The Management Protocol menu allows you to enable or disable Modbus/TCP or BACnet/IP and configure settings for that protocol. Consult your network administrator as needed for these settings. Terminal Emulation (Serial or TCP/IP Connection) / Telnet To activate Modbus/TCP or BACnet/IP: Management Protocol Menu...
  • Page 62: Modbus/Tcp Configuration Menu

    Building Management Functions (IS-IPBML & IS-IPBMS Cards Only) 10.3 Modbus/TCP Configuration Menu Management Protocol Menu ------------------------- Once Modbus/TCP is activated (as described in Section 10.2), 1: Modbus/TCP enabled 2: Modbus/TCP Configuration the Management Protocol menu displays Modbus/TCP as enabled <ESC>: Cancel menu level and provides access to the Modbus/TCP Configuration menu.
  • Page 63: Select Modbus/Tcp Security Mode Menu

    Building Management Functions (IS-IPBML & IS-IPBMS Cards Only) 10.3.1 Select Modbus/TCP Security Mode Menu Management Protocol Menu ------------------------- The Select Modbus/TCP Security Mode menu is used to 1: Modbus/TCP enabled restrict or allow Modbus access to the Web card. 2: Modbus/TCP Configuration <ESC>: Cancel menu level Terminal Emulation Please select a key ?>...
  • Page 64: 10.3.2 Supported Data List - Modbus/Ip

    Building Management Functions (IS-IPBML & IS-IPBMS Cards Only) 10.3.2 Supported Data List - Modbus/IP Modbus/TCP Configuration Menu ------------------------------ The Supported Data List displays a listing of 1: Modbus/TCP Port 2: Modbus Write Access Enabled device data that may be accessed via the 3: Modbus/TCP Security Mode Same Subnet Modbus/IP protocol.
  • Page 65: Bacnet/Ip Server Menu

    Building Management Functions (IS-IPBML & IS-IPBMS Cards Only) 10.4 BACnet/IP Server Menu Management Protocol Menu ------------------------- Once BACnet/IP is activated (as described in Section 10.2), 1: Select Managed Protocol BACnet/IP 2: BACnet/IP Server the Management Protocol menu displays BACnet/IP as enabled <ESC>: Cancel menu level and provides access to the BACnet/IP Configuration menu.
  • Page 66: 10.4.1 Supported Data List - Bacnet/Ip

    Building Management Functions (IS-IPBML & IS-IPBMS Cards Only) 10.4.1 Supported Data List - BACnet/IP The Supported Data List displays a listing of device data that may be accessed via the BACnet/IP protocol. Terminal Emulation (Serial or TCP/IP Connection) / Telnet 1.
  • Page 67: Appendixa - Firmware Updates

    Internet Explorer. Emerson maintains firmware upgrades on its Web site, www.liebert.com/downloads. Emerson manufactures various types of network cards for Liebert products. Before beginning any upgrade, determine the type of Liebert IntelliSlot card to be upgraded.
  • Page 68: Table A3 Communication Settings

    RTCS v2.96.00 Telnet server press the Enter key. Service Port Manager Active 5. Enter the Administrator username and password (both are case- <Esc> Ends Session sensitive): a. Login (username—default is Liebert) Login: Liebert b. Password (default is Liebert) Password: ********...
  • Page 69 Open the Telnet Interface To connect to the card using Telnet: 1. Open a Telnet connection on a computer with an Ethernet connection to the Liebert unit. To do this: • Open a command prompt window—click the Start button, then Run.
  • Page 70 Web Interface To view Web card information using a Web browser: 1. Open a connection to the Liebert IntelliSlot card (if needed, see instructions in A.2.4 - Open the Web Interface). 2. Click on the Support tab, then Summary in the left panel. The Liebert IntelliSlot card model, part number and firmware version appear in the right panel.
  • Page 71 2. Navigate to the Liebert Web site, www.liebert.com/downloads. 3. Choose the firmware upgrade for your card from the selections on the Web page (see A.3.2 - Determine the Liebert IntelliSlot Card Type and Firmware Version). 4. Click on the link to download the file.
  • Page 72 To update the Liebert IntelliSlot card firmware using the HTTP (Web) method: 1. Open a connection to the Liebert IntelliSlot card (if needed, see instructions in A.2.4 - Open the Web Interface).
  • Page 73: Table A4 Firmware Update Settings - Tftp

    7. Choose Exit and Save to save your changes and reboot the card. Reconnect to the Card 8. Connect to the Liebert IntelliSlot card again (if needed, see A.2.3 - Open the Telnet Interface or A.2.1 - Open the Terminal Emulation Interface - Serial Connection).
  • Page 74 4: Factory Settings 5: Firmware Updates Check the new firmware version if you q: Quit and abort changes x: Exit and save wish (see A.3.2 - Determine the Liebert Please select a key ?> IntelliSlot Card Type and Firmware Version).
  • Page 75: Table A5 Firmware Update Settings - Web

    To update the Liebert IntelliSlot card firmware using the TFTP method with a Web interface: Open a Connection to the Card 1. Open a connection to the Liebert IntelliSlot card (if needed, see instructions in A.2.4 - Open the Web Interface).
  • Page 76 When the rebooting is complete, the Web browser window returns to the default opening view. The upgrade is now complete. Check the new firmware version if you wish (see A.3.2 - Determine the Liebert IntelliSlot Card Type and Firmware Version).
  • Page 77: Figure A1 Null Connection

    Transmit Tx (Pin 3) Transmit Tx (Pin 3) Open a Terminal Emulation Connection Firmware Updates Menu 2. Open a connection to the Liebert IntelliSlot card (if ---------------------- 1: XMODEM Update needed, see instructions in A.2.1 - Open the Terminal 2: TFTP Update Emulation Interface - Serial Connection).
  • Page 78 15. In the Send File window, choose 1K Xmodem from the Protocol drop-down list and click Send. A progress window opens, showing the elapsed time and amount of time remaining for the first file to be downloaded to the Liebert IntelliSlot card. The window closes after the first file is down- loaded.
  • Page 79 1: System Information 2: IP Network Settings Check the new firmware version if you wish (see A.3.2 - Determine 3: Messaging the Liebert IntelliSlot Card Type and Firmware Version). 4: Factory Settings 5: Firmware Updates q: Quit and abort changes x: Exit and save Please select a key ?>...
  • Page 80 +39 049 9719 111 Fax: +39 049 5841 257 While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no Asia responsibility and disclaims all liability for damages resulting from use of 29/F, The Orient Square Building this information or for any errors or omissions.