5.4

Web Server

Use the Web Server Menu to configure access to the card
through the Web interface. Consult your network adminis-
trator if needed.
5.4.1

Specify Web Server Settings

Terminal Emulation (Serial or TCP/IP Connection) / Telnet
To change any parameters:
1. Choose IP Network Settings from the Main Menu, then Web Server.
2. Select an option to change, then use the following guide to make changes.
Table 14
Web server settings
Parameter
Web Server
Mode
HTTP
Transport
Port
Password
Protect Site
Configuration/
Control
Refresh
Interval
Web Interface
To access Web Server settings through the Web interface:
• Click on the Configure tab, then Web in the left panel and finally Edit in the right panel. After
making changes, click Save.
Configure tab
Select the operation mode of the Web server.
• Disabled - Web server is disabled
• HTTP - Standard Web port, not encrypted
• HTTPS - Standard secure Web port, all communication is encrypted
Web Server listening port number.
• For HTTP mode (non-encrypted communications), the default port is 80.
• For HTTPS mode (encrypted communications), the default port is 443.
For HTTPS, you must also install a security certificate for Internet Explorer. Refer to the appro-
priate section for your version of Internet Explorer:
• 5.4.2 - Install Security Certificates - Internet Explorer 6 or earlier
• 5.4.3 - Install Security Certificates - Internet Explorer 7 or later
When enabled, the entire site is password-protected. (If disabled, all pages are accessible
without a password except configure and control functions.)
Enable or disable the use of a Web browser to perform configuration and control operations.
Note: This feature affects configuration and control operations from the Web interface only. If
disabled, these functions may still be available using other system interfaces.
The interval in seconds (10 to 600 seconds) between automatic updates of dynamic Web
pages—parametric data and device status in the right panel.
RECOMMENDATION: Consider whether frequent updates will slow down the system. If many
users will access the device simultaneously, select a larger value to best serve all users.
Recommended values range from 20 to 60 seconds.
Web
Web Server Menu
----------------
1: Web Server Mode
2: HTTP Transport Port
3: Password Protect Site 'disabled'
4: Configuration/Control 'enabled'
5: Refresh Rate
<ESC>: Cancel menu level
Please select a key ?>
Description & Valid Settings
Edit
27
Network Settings
HTTP (Not Secure)
80
30
seconds