Empire Comfort Systems DVP42 Series Installation Instructions And Owner's Manual page 19

Direct vent zero clearance gas fireplace heater
Table of Contents

Advertisement

SEE FIGURE 22 FOR
PERMISSIBLE "H" AND "V"
DIMENISONS.
MINIMUM HOLE LOCATION DIMENSIONS FOR THROUGH THE
WALL HORIZONTAL INSTALLATIONS WITH 90 DEGREE ELBOW
OFF TOP OF FIREPLACE
FIREPLACE
HARD ELBOW DIMENSIONS
SERIES
"A"
DVP42FP
43-1/2"
(1105mm)
DVP48FP
43-1/2"
(1105mm)
FIREPLACE
FLEX PIPE 90 DEGREE BEND
SERIES
"A"
DVP42FP
46"
(1143mm)
DVP48FP
46"
(1143mm)
Positioning the Fireplace
Determine the exact position of the appliance so the direct vent
termination will be centered (if possible) between two studs. This
will avoid any extra framing. All vent kit pipes should be assembled
on the unit after the unit is moved into the final position.
Cutting the Hole
After the fireplace has been positioned in its permanent location,
the hole through the exterior wall of the house can be cut. This hole
must be 12" (305mm) high x 10" (254mm) wide with its center line
determined by the amount of vertical rise and horizontal run of the
termination. See Figure 26. When locating the hole it must be noted
that the bottom of the cap must be 12" (305mm) above the ground
level, and top of the cap must be no less than 18" (457mm) below a
combustible projection, and no closer than 9" (229mm) to any wall
running parallel to vent termination. See Figure 27.
31455-4-1113
VENTING FIREPLACE - TOP
Figure 26
"B"
"C"
5"
7"
(127mm)
(178mm)
5"
7"
(127mm)
(178mm)
"B"
"C"
5"
7" (178mm)
(127mm)
5"
7"
(127mm)
(178mm)
Figure 27
Figure 28
Page 19