Chapter 4: E2 Controller
Figure 4-47. Calibration screens.
A Static Pressure Offset screen only appears if your unit is configured for static pressure control.
Figure 4-48. Static Presure Offset screen.
Additional sensor offset screens are available for optional sensors if enabled at the factory such as Remote Supply Air Temp and
Remote Supply Air Humidity.
NOTE: When calibrating sensors, an offset at one extreme may produce an error at the other extreme. Always verify that any
offset is valid over the entire range of the sensor.
4.5.5.5 Blower
Figure 4-49. Blower screen.
From the Service>Blower menu you may access screens to view/set up the static pressure if applicable and adjust the blower
speeds.