Boolean Values For Http, Snmp/Modbus Coils/Binary Values For Bacnet - Black Box CRCW-12 User Manual

Cold row chilled water (cw)
Table of Contents

Advertisement

Chapter 4: E2 Controller
Variable/Value Descriptions
Variable
Description for
Description
Value 0
Fan link control
None
[X] fan speed
Manual
control
Type of unit
Not selected

4.9.3 Boolean Values for HTTP, SNMP/Modbus Coils/Binary Values for BACnet

Table 4-31. Boolean Values for HTTP, SNMP/Modbus Coils/Binary Values for BACnet.
BMS
Address
1
r
3
4
5
6
100
101
102
103
104
105
106
Page 102
Table 4-30. Variable/Value Descriptions.
Description for
Description for
Value 1
Value 2
Upper & middle
Upper & lower
Temperature
Variance from
proportionate
average
CW-12"
CW-24"
Modbus
BACnet
Address
Address
Description
002
1
Global alarm output
003
2
System on status
004
3
Airflow has been proven
005
4
Call for cooling
006
5
Call for humidification
007
6
Call for dehumidification
101
100
BMS value to pause the unit
102
101
BMS value to reset alarms
103
102
Force rotation of units in group manual or BMS
104
103
BMS value to switch CW sources
105
104
BMS value to switch dual power primary
106
105
BMS value to activate lockout function
107
106
Reset dirty filter alarm
724-746-5500 | blackbox.com
Description for
Description for
Value 3
Value 4
Middle & lower
All
AR-12"
AR-24"
Default
0
0
0
0
0
0
0
0
0
0
0
0
0
Description for
Description for
Value 5
Value 6
W/G-12"
W/G-24"
Direction
R
R
R
R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W