Signed Values For Http, Snmp/Modbus Holdling Registers/Analog Values For Bacnet - Black Box CRCW-12 User Manual

Cold row chilled water (cw)
Table of Contents

Advertisement

Chapter 4: E2 Controller
4.9.1 Signed Values for HTTP, SNMP/Modbus Holding Registers/Analog Values for BACnet
Table 4-28. Signed Values for HTTP, SNMP/Modbus Holding Registers/Analog Values for BACnet.
BMS
Modbus
Address
Address
1
002
2
003
3
004
4
005
5
006
6
007
7
008
8
009
9
010
10
011
11
012
12
013
13
014
14
015
15
016
16
017
17
018
18
019
19
020
20
021
100
101
101
102
102
103
103
104
104
105
105
106
Page 100
BACnet
Address
Description
1
Temperature setpoint
2
Humidity setpoint
3
Average supply temperature display value
4
Return humidity sensor current value
5
Dewpoint of return temperature and humidity
6
Dewpoint of remote temperature and humidity
7
Middle fan speed
8
Upper fan speed
9
Lower fan speed
10
Middle fan manual speed
11
Upper fan manual speed
12
Lower fan manual speed
13
Static pressure sensor current value
14
C1 discharge pressure sensor current value
15
C1 suction pressure sensor current value
16
C1 suction temperature sensor current value
17
Return temperature display value
18
Remote temperature display value
19
Entering water temperature display value
20
Leaving water temperature display value
100
High air temperature alarm limit
101
Low temperature alarm limit
102
High humidity alarm limit
103
Low humidity alarm limit
104
High water temperature limit
105
Low water temperature alarm limit
724-746-5500 | blackbox.com
Default
Read/Write
72.0
R/W
45.0
R/Ws
0.0
R
0.0
R
0.0
R
0.0
R
0.0
R
0.0
R
0.0
R
0.0
R/W
0.0
R/W
0.0
R/W
0.0
R
0.0
R
0.0
R
0.0
R
0.0
R
0.0
R
0.0
R
0.0
R
80.0
R/W
60.0
R/W
70.0
R/W
30.0
R/W
60.0
R/W
40.0
R/W