4.9.8 Unsigned Values for HTTP, SNMP/Modbus Holding Registers/Analog Values for BACnet
Table 4-36. Unsigned Values for HTTP, SNMP/Modbus Holding Registers/Analog Values for BACnet.
BMS
Address
100
101
102
103
4.9.9 Boolean Values for HTTP, SNMP/Modbus Coils/Binary Values for BACnet
Table 4-37. Boolean Values for HTTP, SNMP/Modbus Coils/Binary Values for BACnet.
BMS
Modbus
Address
Address
100
101
101
102
102
103
103
104
104
105
Modbus
BACnet
Address
Address
Description
229
1100
BMS keep alive parameter
230
1101
BMS low fan speed for CW units
231
1102
BMS run fan speed for CW units
232
1103
BMS dehum fan speed for CW units
BACnet
Address
Description
1100
BMS value to pause the unit
1101
BMS value to reset alarms
1102
Force rotation of units in group manual or BMS 0
1103
BMS value to switch CW sources
1104
BMS value to switch dual power primary
724-746-5500 | blackbox.com
Chapter 4: E2 Controller
Default
Direction
0
R/W
0
R/W
0
R/W
0
R/W
Default
Direction
0
R/W
0
R/W
0
R/W
0
R/W
0
R/W
Page 107