Chapter 4: E2 Controller

4.9.7 Digital Output Packed Bit Variables

The R/W BMS variables fall into two categories. Variables like the temperature setpoint are permanent. As permanent variables,
they retain their value regardless of power loss or BMS communications failure. The controller's flash memory is limited to one
million write cycles for permanent variables. The other category is the integer and digital variables that start with "BMS." These
are expected to be changed frequently and require that the BMS is active when changing them. All BMS variables require that the
BMS "keep alive" parameter (Variable 100) changes between 1 and 2 within a 10-minute span. The general procedure is to set
up variables like the BMS low fan speed and then write a 1 to the BMS "keep alive" address. If the controller does not see a 2
written to the BMS "keep alive" address within 10 minutes, all the BMS variables will revert to their previous values.
Page 106
Table 4-35. Digital Output Packed Bit Variables.
Bit
Digital Outputs 1
0
Global alarm
1
Custom alarm 1
2
Master fan enable
3
DX1 enable
4
DX1 liquid line solenoid
5
Humidifier enable
6
Dual power output A
7
Dual power output B
8
Pump enable
9
Custom alarm 2
10
Custom alarm 3
11
Reserved
12
Reserved
13
Reserved
14
Reserved
15
Reserved
724-746-5500 | blackbox.com
Digital Outputs 2
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved

Advertisement

Table of Contents
loading

This manual is also suitable for:

Crcw-24

Table of Contents