E5CN
CHARACTERISTICS
Indication accuracy
Hysteresis
Proportional band (P)
Integral time (I)
Derivative time (D)
Control period
Manual reset value
Alarm setting range
Sampling period
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Weight
Protective structure
Front panel
Rear case
Terminals
Memory protection
EMC
Approval standards
Note: The indication of K thermocouples in the -200 to 1300°C range, and T and N thermocouples at a temperature of -100°C or less,
and U and L thermocouples at any temperature is ±2°C±1 digit maximum. The indication of B thermocouples at a temperature of
400°C or less is unrestricted.
The indication of R and S thermocouples at a temperature of 200°C or less is ±3°C±1 digit maximum.
Thermocouple:
(
0.5% of indicated value or
Platinum resistance thermometer:
(
0.5% of indicated value or
Analog input:
0.5% FS
1 digit max.
CT input:
5% FS
1 digit max.
0.1 to 999.9 EU (in units of 0.1 EU)
0.1 to 999.9 EU (in units of 0.1 EU)
0 to 3999 s (in units of 1 s)
0 to 3999 s (in units of 1 s)
1 to 99 s (in units of 1 s)
0.0% to 100.0% (in units of 0.1%)
-1999 to 9999 (decimal point position depends on input type)
500 ms
20 MΩ min. (at 500 VDC)
2000 VAC, 50 or 60 Hz for 1min (between different charging terminals)
2
10 to 55 Hz, 10 m/s
for 2 hours each in X, Y and Z directions
2
300 m/s
, 3 times each in 3 axes, 6 directions (relay: 100 m/s
Approx. 150 g
NEMA4 for indoor use (equivalent to IP66)
IP20
IP00
EEPROM (non-volatile memory) (number of writes: 100,000)
Emission Enclosure:
Emission AC Mains:
Immunity ESD:
Immunity RF-interference:
Immunity Conducted Disturbance:
Immunity Burst:
UL3121-1, CSA22.2 No. 14, E.B.1402C
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
Conforms to VDE0106/part 100 (Finger Protection), when the terminal cover is mounted.
1 C, whichever greater)
1 digit max. (See Note.)
1 C, whichever greater)
1 digit max.
2
Mounting bracket: Approx. 10g
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
ENV50140:
10 V/m (amplitude modulated,
80 MHz to 1 GHz) (level 3)
10 V/m (pulse modulated, 900 MHz)
ENV50141:
10 V (0.15 to 80 MHz) (level 3)
EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
E5CN
)