Installing and Wiring the Thermostat

Mounting the Thermostat into the Base Plate

The Proliphix thermostat contains jumpers to configure the HVAC power settings.
The power settings determine which HVAC power source (RH or RC) is configured to
turn on each HVAC system (cool, heat and fan). Most applications use only RH
power. The Proliphix thermostat is shipped from the factory with the "RH Only"
configuration.
Table 5
J1 inserted.
Table 5 HVAC Power Configuration
HVAC Power Configuration
RH only (default) – Supplies W1, W2, Y1, Y2, G
RC only – Supplies W1, W2, Y1, Y2, G
RH and RC – RH supplies W1, W2, G and RC supplies Y1
and Y2
RH and RC – RH supplies W1 and W2 and RC supplies Y1,
Y2, G
The NT100e/NT120e/NT125e can be powered from different sources presented on the
following Ethernet CAT5/5E/6 interface:
Table 6
sources.
Table 6 NT100e/NT120e/NT125e Power Source Configuration
HVAC Power Configuration
PoE Power Source
EPA-20/60 Power Source
Figure 5
jumper in J2 supports an Up (POS1) or Down (POS2) position. The example in
Figure 5
downward to the POS2 position.
10
lists the possible HVAC power configurations. RC and RH are connected with
A Power over Ethernet (PoE) source is an Ethernet router, switch, or mid-span
device that complies with the 802.3af Power over Ethernet standard.
Proliphix Ethernet Power Adapters (EPA) are multi-port power injectors capable
of supplying power to either two (EPA-20) or six (EPA-60) Proliphix Network
Thermostats.
shows how to configure the NT100e/NT120e/NT125e for two different power
shows the location of the jumpers on the thermostat circuit module. The
shows the J2 jumper in the Up position. If necessary, move the jumper
Beta Draft Confidential
Proliphix Thermostat Installation Guide, Release 1.0
J2
J1
POS1
IN
POS1
IN
POS1
OUT
POS2
OUT
J3
Out
In
Part No. 600-01000-100