Wiring The Base Plate Terminals; Fuel Burner Hvac - Proliphix Thermostat Installation Manual

Table of Contents

Advertisement

Installing and Wiring the Thermostat

Wiring the Base Plate Terminals

Use the instructions in this section to wire the base plate terminals as follows:

Fuel Burner HVAC

Use the instructions in this section and refer to
plate for fuel burner HVAC. Refer to the labels you placed on the wires when you
removed the existing thermostat
Table 1
required to support the single-stage and dual-stage application.
Table 1 Fuel Burner Terminal Conversion Chart
Standard
Terminal
R, RH
RC
C
W, W1
Y, Y1
W2
Y2
G
-
-
a
4
Wire the NT10e/NT20e base plate for fuel burner HVAC
HVAC
(page
6).
Wire the NT100e/h, NT120e/h, NT125e/h, and NT150e/h for fuel burner HVAC
(page
4) and heat pump HVAC
lists the standard HVAC terminal label and the corresponding Proliphix label
Proliphix
Terminal
RH
RC
C
W1
Y1
W2
Y2
G
S1+ or
CM
H
For "h" thermostat models only, the 24VAC common must be in the same AC phase as the 24VAC
source (RH or RC). If the thermostat is connected to RH only, or RH and RC then C must be the RH
common. If the thermostat is connected to RC only then C must be the RC common.
Beta Draft Confidential
(page
6).
Table 1
(page
2).
NT10e/NT20e
NT100e/h, NT120e/h, NT125e/h,
and NT150e/h
24VAC source
24VAC source
24VAC source
24VAC source
Not used
Not used or 24VAC common
Heat relay
Stage 1 heat relay
Cool relay
Stage 1 cool relay
Not used
Stage 2 heat relay
Not used
Stage 2 cool relay
Fan relay
Fan relay
Not used
Contact closure common (NT150 only)
Not used
Contact closure, Active open or Active closed
(NT150 only)
Proliphix Thermostat Installation Guide, Release 1.0
(page
4) and heat pump
and
Figure 1
to wire the base
a
Part No. 600-01000-100

Advertisement

Table of Contents
loading

Table of Contents