The combustion performance must be checked before
and after any servicing work on the combustion and
burner components. Refer to section 8.2.
Checking the ionisation current,
Service Function 3.3
B Select Service Function 3.3. (See page 32 "Display-
ing Service Functions")
If the display shows 2 or 3, the ionisation current is OK.
If the display shows 0 or 1, the electrode assembly
(32.1, page 6) must be cleaned or replaced.
Primary Heat exchanger
There is a special accessory kit (no. 840) for cleaning
the heat exchanger, order no. 7 719 001 996.
B Check control pressure on the air - gas mixer unit at
max. rated heat output using an electronic manome-
ter.
Fig. 45
The heat exchanger should only be
i
cleaned if the control pressure is
2.2 mbar (depression) or less.
B Remove cleaning access cover (415, page 6) and
the metal plate below it, if present. Refer to fig. 2.
B Unscrew condensation trap and place suitable con-
tainer underneath. Refer to fig. 46.
38
B Remove the fan and the burner as described in the
Fig. 46
B Loosen any deposits in the heat exchanger from top
Fig. 47
6 720 610 332-69.1R
B Clean the heat exchanger from top to bottom using
Fig. 48
B Flush the heat exchanger from the top. Refer to
text headed "Burner" (see page 39).
to bottom using the cleaning blade. Refer to fig. 47.
6 720 610 332-73.1R
the brush. Refer to fig. 48.
fig. 49.
6 720 610 332-72.1R
6 720 610 332-74.1R