3.3

Siting the appliance

Regulations concerning the Installation Site
B Relevant national regulations must be complied with
section 3.8.1.
B Consult the installation instructions for details of min-
imum clearances required.
Combustion air
In order to prevent corrosion, the combustion air must
not contain any corrosive substances.
Substances classed as corrosion-promoting include
halogenated hydrocarbons which contain chlorine and
fluorine compounds and are contained in some sol-
vents, paints, adhesives, aerosol propellants and house-
hold cleaners, for example.
6 720 611 449 GB (03.11)
Surface temperature
The max. surface temperature of the casing and the flue
is less than 85 °C.
This means that, no special safety precautions are
required with regard to flammable building materials
and fitted furniture. The specified clearances must be
maintained.
Cupboard/Compartment
The appliance can be installed in a cupboard/compart-
ment need for airing clothes providing that the require-
ments of BS6798 and BS5440:2 are followed. The low
casing losses from the appliance eliminate the need for
ventilation openings in the compartment.
Installation
13