Page 2
Because of this you should monitor your new unit during initial operation. Make sure that it has been properly installed and is operating to your satisfaction. Consult your HygroMatik specialists. We will test the quality of your water and advise you on installation and initial operation. Your HygroMatik steam humidifier will be carefully adapted to your particular application.
They will impress you with their safety, ease of use and econom- ical operation. In order to operate your HygroMatik steam humidifier safely, properly and efficiently, please read these operating instructions. Employ your steam humidifier only in sound condition and as directed.
C2: Range of high conductivity (adjustments recommended) D2: Upper threshold Warning: HygroMatik steam humidifiers emit steam with a tem- perature of 100° C. The steam may not be inhaled directly. The HygroMatik Steam Humidifier is not designed for outdoor fit- ting 1.2 Typographic Distinctions •...
If the product is resold, turn the documenta- tion over to the new operator. If the documentation is lost, please contact HygroMatik. Versions in Other Languages These operating instructions are available in several languages. If interested, please contact HygroMatik or your HygroMatik dealer. Page 7...
2. Safety Notes 2.1 Overview These safety notes are required by law. They promote work- place safety and accident prevention. Warnings and Safety Symbols The safety symbols below identify sections containing warnings about hazards or potential dangers. Please familiarize yourself with these symbols.
Attention: In the event of leaky or faulty components uncon- trolled hot steam may flow. HygroMatik steam humidifiers are IP20-protected. Make sure that the unit is protected from drips in its installed location. Installing a humidifier in a room without water discharge requires safety devices to protect against water leakages.
3.3 Packing Note: Notice the symbols affixed to the packing box. 3.4 Interim Storage Store the unit in a dry place and protect from frost. 3.5 Check for Complete and Correct Delivery of Goods Upon receipt of the unit, confirm that: •...
4. Operation and Installation 4.1 Mode of Operation The HygroMatik steam humidifier utilizes the conductivity nor- mally present in tap water for steam production. Electrodes inside an enclosed steam cylinder are immersed directly into the tap water. They are connected to the alternating current.
Page 13
Please also see Section „Exploded View“. Location Designation adapter vent pipe max. water level sensor electrode water drain, discharge top part of steam cylinder o-ring cylinder flange cylinder flange and o-ring lower part of cylinder solenoid valve water inlet blow-down pump o-ring cylinder base electrodes...
Page 14
The concentration of dissolved salts increases over time, which can lead to a rise in the conductivity of the water. If this contin- ues, conductivity may increase until a short circuit occurs. This could damage the unit, but in any case would significantly reduce the life span of the electrodes.
The minimum clearances indicated in the diagram below must be observed; these are necessary to ensure adequate ventilation for the housing. • HygroMatik humidifiers are not suitable for direct out- door installation. • The steam humidifier should be installed as close as possible to the steam manifold.
5.1.1 Fitting measures Clearances Note: When choosing the site for the steam humidifier, consider the location of existing water installations (feed and drain lines). Page 16...
5.2 Fan Unit (optional) Note: The fan unit should be positioned to avoid drafts. In gen- eral, a minimum height of 2 m is sufficient. Install the fan unit directly on a wall. Fan Unit Type for wall installation VG 08, 17, 30 Warning: •...
5.3 Absorption Distance B The "absorption distance" (B ) is defined as the distance from the steam feed to where the steam is completely absorbed in the treated air. Inside the absorption distance, steam is visible as mist in the air stream. Condensation may collect on anything installed inside the absorption distance.
Page 20
Length I of the usable steam manifold depends on the dimen- sions of the air duct. The length of the absorption distance can be reduced by using multiple steam manifolds (also see section on the steam manifold). Method: Graphically determine absorption distance B using the absorp- tion distance nomogram (also see Section „Absorption Distance Nomogramm“).
5.4 Steam Manifold 5.4.1 Notes on Installation These notes are based on a homogeneous Horizontal installation of Standard steam manifold installation: steam manifold Duct Steam Manifold Air flow L1=L2=L3 An even distribution of steam manifolds ensures a uniform steam distribution. Please use the total hight of the duct! Steam Manifold Air flow...
Page 23
Air duct Positioning of steam manifolds Sample flat Staggered vertically and laterally Air flow very flat By tilting the steam manifold 30 - 45° very flat duct towards the air flow direction, the mini- mum upper clearance can be reduced to 70mm.
Page 24
With high-pressure air-conditioning systems, the unit's drain hose system must be modified depending on the over pressure. When this is the case please consult HygroMatik. • Install the steam manifold as close as possible to the steam humidifier in order to minimize steam loss through condensation.
Page 25
2x(2xDN40) 2x(1xDN40) 2x(1xDN12) * For units HL 6 - 12 and HC3-12 HygroMatik delivers one adapter DN40 / 25 (but not for SPA applications).. ** For units HL 36 - 45 HygroMatik delivers one t-connector for separating the steam on two steam manifolds.
Note: When installing the steam hose, please pay attention to the following: • The steam hose diameter may not be smaller than the steam outlet of the HygroMatik steam humidifier (do not restrict the cross-section, otherwise back pressure will increase). •...
5.6 Cover Plate HygroMatik flange plates may be used to neatly complete instal- lation of the steam humidifier in the air duct. Two-piece flange plates are available for the DN25 and DN40 steam manifolds. flange plate DN25 E-2604260 flange plate DN40 E-2604410...
5.8 Condensate Hose Note: When installing the condensate hose, please pay atten- tion to the following: Warning: To keep condensate from accumulating in the duct, make sure condensate can drain freely. If the steam manifold is positioned higher than 500 mm above the steam humidifier: »...
Page 31
» If enough space is available, lay a loop as a vapor trap. The steam manifold must be at least 500 mm from the loop. If the steam manifold is positioned lower than 500 mm above the steam humidifier: » Lay steam hose at a height of at least 400 mm above unit and then connect to the steam manifold with a con- stant fall.
5.10 Steam Solenoid Valves When humidifying a number of loads, which are to be controlled separately, using a single steam humidifier, steam solenoid valves can be included in the steam hoses. Valve control has to provided by the customer. • Install the vertical risers with flow from bottom to top.
For water installation please use the water connecting hose that is delivered with the unit. 6.1 Operation with Softened Water Warning: Unless special measures are taken, feeding softened water into the HygroMatik steam humidifier is dangerous. It can cause • unacceptably high conductivity •...
Note: Please contact HygroMatik if you wish to operate the unit with softened water. If using a water softening system, we recommend diluting the softened water with normal tap water to produce an overall hard- ness between 4-8°dH. This value can be set lower if the water does not foam.
» Use a cap nut (internal thread ¾“) with inner seal for a customer-provided water installation. 6.3 Water discharge min.: 250mm max.: 1000mm Warning: During blow down hot water with a temperature of about 95°C is being drained. If touched this can cause burns to the skin.
There is a 3mm-wide crack between the pump drain hose jacket and the inner surface of the housing drain connection. If water collects in the base plate, it will flow through this crack into the drainage system. 6.4 Water Installation Check Go down the following water installation checklist: ...
7. Electrical Connection Danger, Hazardous Voltage: All work related to electrical instal- lation to be performed by authorized personnel only (electricians or professionals with equivalent training). The customer is responsible for checking qualifications. Danger, Hazardous Voltage: Do not plug the steam humidifier into the power grid until after all installation work has been com- pleted.
Page 38
2 x 32,5 A 6 x 35 A HY90 2 x 48,8 A 6 x 63 A HY116 2 x 62,8 A 6 x 63 A CompactLine: Type Power Usage Circuit Protection 3,3A 1 x 6A 6,5A 1 x 10A...
MiniSteam: Type Power Usage Circuit Protection MS5, 230V/1/N 15,7 A 1 x 16 A MS5, 400V/3/N 5,4 A 3 x 6 A MS10, 400V/3/N 10,8 A 3 x 16 A DBE: Type Power Usage Circuit Protection DBE1 3,3 A 1 x 6 A DBE2 6,5 A 1 x 10 A...
7.3 Fan Unit » Connect fan unit according to the wiring diagram. The fan unit operates in parallel with the humidifier. Note: Terminals 37 and 38 are only installed if the option „fan unit“ is ordered. Page 40...
7.4 Safety Interlock Note: Install contact interlocks, i.e. max. hygrostat, vane relay, pressure controller, air interlock, in series between terminals 1 and 2. Warning: A max-hygrostat should be installed in the safety inter- lock. The max-hygrostat acts as a safety device in case the humidity sensor malfunctions.
8. Commissioning Warning: This unit is only to be started by qualified personnel. Switching off steam humidifier Warning: Before starting up the unit, make sure you know how to switch it off. » Switch off unit by setting control switch to “0” »...
9. Maintenance The HygroMatik steam humidifier is easy to maintain. However, inadequate or improper maintenance can lead to operational malfunctions. Perform regular maintenance to give your unit a long life span. Warning: When performing maintenance work, please note: • During operation and also for a while after switching off the unit the steam cylinder is hot.
In extreme cases, water pretreatment may be necessary (soft- ening by dilution to approx. 4 - 8 °dH; decarbonization/partial desalination to achieve target reductions in carbonate hard- ness). HygroMatik would be pleased to refer you to companies specializing in water treatment systems. 9.2 Access Electrical Enclosure »...
9.3 Removing and Cleaning the Steam Cylinder Warning: Please follow the detailed instructions in these operat- ing instructions! The unit is only to be serviced by qualified, authorized personnel. Note the warnings and safety notes in the operating instructions. Failure to observe warnings and safety notes may result in injury, serious injury or death, and/or dam- age to the unit.
Page 46
check for voltage remove stopper disconnection disconnect unit from completely drain the cylinder water supply remove steam check cylinder temperature hose from adapter push clip on adapter lift steam cylinder out of base outside cabine Page 46...
Page 47
unplug electrodes / remove flange clamps sensor electrode open cylinder remove used O-ring clean cylinder inside. Do not use acids or other chemicals. clean strainer Warning: Check the inside of the top part of steam cylinder for crust build-up and possible salt bridges (black grooves between the electrode leads).
Page 48
connect upper and lower insert new O-ring part with clamps Note: When putting the cylinder back together, the joints and reinforcements of both sections must fit together snugly. remove used O-ring insert new O-ring remove old O-ring, connect plug to level insert new O-ring sensor / electrodes Page 48...
Page 49
place cylinder vertically into cylinder base Warning: Before attaching the electrode plugs please make sure that they are free of corrosion. If not please replace them. The plug must be pressed down onto the electrode as far as it will go. Note: Connect plugs to the correct electrodes.
open water supply check for leakages close cabinet Warning: The unit must be closed and locked. This guarantees that the cover is grounded. (Only with hymidifier type HyLine and MiniSteam) Switch on the unit and check for leaks after 15-30 minutes of operation.
The humidifier switches itself off. Also see Section "Mainte- nance." When the electrodes are less than 1/3 to 1/2 of their original length, replace them. 9.4.1 Original Electrode Lengths Original lengths of HygroMatik large area stainless-steel elec- trodes are: HyLine: Type...
Page 52
» Loosen knurled nuts (5) and remove electrodes (48). » Install new electrodes and hand tighten the nuts. Use solvent-free, HygroMatik-quality o-rings (for flange, cylinder base and steam hose adapter). » Assemble steam cylinder and place it into cylinder »...
• there is "lightning" in the cylinder, the conductivity of the water is too high or it isn't decanted often enough. In this case please contact HygroMatik. 9.6 Cleaning the Blow- Down Pump » Remove cylinder »...
9.7 Cleaning the Water Inlet Solenoid Valve Removal » Shut off water supply and loosen water installation hose connection. » Remove cylinder please also see chapter „Removing and Cleaning Steam Cylinder“ » Loosen connecting hose (21) from the base. » Detach e-cable from the solenoid valve.
9.9 Checking Hoses Since steam and condensate hoses are also subject to wear they have to be checked regularly. 9.10 Checking Operation Start up the unit and operate for a few minutes at maximum out- put if possible. » Check safety devices. »...
C01 C02 C06 C10 C17 C2 2 C30 C45 C58 Article No. Description E-321602 2 Cylinder flange clamp E-322000 0 Cylinder b ase DN 20/25i/15/12 E-220608 6 Cylinder b ase DN 40/25i/15/12 B-321602 3 Mounting set for cylinde r base B-221402 3 Mounting set for cylinde r base E-321602 0 Conden sate cap DN9 E-220403 5 Conden sate cap DN1 2...
Page 59
C01 C02 C06 C10 C17 C2 2 C30 C45 C58 Article No. Description E-322000 5 O-ring for pump - cylin der base E-322000 5 O-ring for pump - ada pter B-240402 7 Drain pump without mounting set E-240402 4 O-ring for drain pump (cover-motor) E-242042 3 Drain hose 1 1/4"...
Page 60
C01 C02 C06 C10 C17 C2 2 C30 C45 C58 Article No. Description Control, electrical supply below 230V E-250409 2 Main contactor 100 A, 2 30V B-250708 1 Main contactor 65A, 230V B-250706 1 Main contactor 35A, 230V B-250704 1 Main contactor 20A, 230V B-252420 9 Cable for electrode 35A/6mm²...
12. Fax Form - Order for spare parts Fax Form Please copy, fill in and fax to HygroMatik GmbH Lise-Meitner-Str. 3 . +49(0)4193/895-31 Fax.No 24558 Henstedt-Ulzburg Tel. +4904193/895-0 Order of spare parts unit type *______________ serial no.* ___________________ commission: ______________ order no.: __________________...